ENGLISH On/Off settings Battery settings Submenu Cold start Forced reboot Auto restart Energy saving Sleep mode Remote command Available settings [Disable] [Enable] Enables the product to be started on battery power. First cold start always disabled. [Disable] [Enable] If mains recover during a shutdown sequence: - if enabled, shutdown sequence will complete and wait 10 seconds prior to restart - if disabled, shutdown sequence will not complete and restart will occur immediately. [Disable] [Enable] Enables the product to restart automatically when mains recovers after a complete battery discharge. Default settings Enable Enable Enable [Disable] [Enable] If enabled, UPS will shut down after 5min of back-up time, if no load is detected on the output. [Disable] [Enable] If disabled, LCD and communication will turn OFF immediately after UPS is OFF. If enabled, LCD and communication stays ON 1h30 min after UPS is OFF. Disable Disable [Disable] [Enable] Enable If enabled, shutdown or restart commands from software are authorised. RPO delay Automatic battery test [0 s] [1s ] [2 s]...[180 s] Delays remote power off command [No test] [Every day] [Every week] [Every month] Available only if battery charge mode is set to constant charge. Low battery warning [1 %] [2 %] ... [100 %] The alarm triggers when the set percentage of battery capacity is reached during a back-up time. Restart battery level [1 %] [2 %] ... [100 %] If set, automatic restart will occur only when percentage of battery charge is reached. [0 s] Every week(in constant charge, otherwise following ABM battery test method) 20 % 0% Battery charge mode [ABM cycling] [Constant charge] ABM cycling External battery [Auto detection] [Manual EBM set.] [Manual battery set.] Deep discharge protection [Yes] [No] If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. [Auto detection] Using standard EBM, UPS detects automatically the number of EBM connected Yes 5P 750VA-1.5 KVA US_EN Page 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

Page 11
5P 750VA-1.5 KVA US_EN
ENGLISH
Submenu
Available settings
Default settings
On/Off settings
Cold start
[Disable] [Enable]
Enables the product to be started
on battery power.
First cold start always disabled.
Enable
Forced reboot
[Disable] [Enable]
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
immediately.
Enable
Auto restart
[Disable] [Enable]
Enables the product to restart
automatically when mains recovers
after a complete battery discharge.
Enable
Energy saving
[Disable] [Enable]
If enabled, UPS will shut down after
5min of back-up time, if no load is
detected on the output.
Disable
Sleep mode
[Disable] [Enable]
If disabled, LCD and communication
will turn OFF immediately after
UPS is OFF.
If enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command
[Disable] [Enable]
If enabled, shutdown or restart commands
from software are authorised.
Enable
RPO delay
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[0 s]
Battery settings
Automatic battery
test
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge
mode is set to constant charge.
Every week(in constant charge,
otherwise following ABM
battery test method)
Low battery warning [1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0%
Battery charge mode [ABM cycling] [Constant charge]
ABM cycling
External battery
[Auto detection] [Manual EBM set.]
[Manual battery set.]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.
Yes