OUTDOOR-COOKING 30"W. Ultra-Premium T-Series/E-Series Gas Grill Installation Requirements VGBQ300-2RT2 Ultra-Premium T-Series Two-Burner Grill VGBQ300-2RE2 Ultra-Premium E-Series Two-Burner Grill UTILITY REQUIREMENTS GAS Fixed piping installations • Check with local gas utility company or with local codes for instructions on installing gas supply lines. All gas connections should be made by a competent technician and in accordance with local codes and or ordinances. In the absence of codes, the installation must comply with the National Fuel Gas Code ANSI Z223.1. • An installer-supplied gas shutoff valve must be installed in an easily accessible location. All installer-supplied parts must conform to local codes. • Must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of that system at test pressures equal to or less than 1/2 psi (3.5 kPa). Natural gas models • Water column pressure o Operating pressure-4.0" WCP o Supply pressure of 6" - 10" WCP o If incoming pressure exceeds 10" WCP, a step-down regulator is required. • Accepts standard residential 1/2" (1.3 cm) ID gas service line; 1/2" (1.3 cm) NPT male with 7/8" (2.2 cm) flare adapter. o If using a Viking GSH12 flexible hose, remove the 1/2" (1.3 cm) flare adapter and attach hose to the 7/8" (2.2 cm) male flare on the regulator assembly. LP/propane models • Water column pressure o Operating pressure- 10" WCP o Supply pressure of 11" - 14" WCP (for fixed piping installations) o If incoming pressure exceeds 14" WCP, a step-down regulator is required. • Accepts standard residential 1/2" (1.3 cm) ID gas service line; 1/2" (1.3 cm) NPT male with 3/8" (0.95) flare adapter. LP/propane tank installations • Water column pressure o Operating pressure- 10" WCP • Includes high-capacity hose/regulator assembly for connection to a standard 5gal./20-lb. (approx. 12" diameter/18"H.) LP/propane gas cylinder equipped with a Type 1, QCC-1 connector o The cylinder connection device must be compatible with the Type 1, QCC-1 connector on the outdoor cooking appliance. o The cylinder must be provided with a shut-off valve terminating in an LP/propane Standard SS grill burners (each) Gourmet-Glo™ rotisserie burner VGBQ300-2RT/E2 25,000 BTU (7.3 kW) Nat./22,500 BTU (6.5 kW) LP (T-Series) 29,000 BTU (7.3 kW) Nat./28,000 BTU (6.5 kW) LP (E-Series) 15,000 BTU (4.4 kW) Nat./13,500 BTU (4.0 kW) LP gas supply cylinder valve outlet specified. o The cylinder supply system must be arranged for vapor withdrawal and provided with a listed OPD (overfilling prevention device). ELECTRICAL • T-Series models o 9-volt DC battery for electronic ignition o Rotisserie motor max. amp usage-6.0 • E-Series models o 3' (91.4 cm) power cord supply cord with 3-prong grounded plug attached to grill • 120 VAC/60 Hz o Grill max. amp usage • VGBQ300-2.1 o 2' (61.0 cm) power cord supply cord with 3-prong grounded plug attached to rotisserie motor. • 120 VAC/60 Hz o Rotisserie motor max. amp usage-6.0 PLUMBING Not applicable Surface burner rating PLANNING AND DESIGN GUIDE VIKINGRANGE.COM • 1-888-VIKING1 REVISED 5/16/11 ©2011 VRC-INFORMATION SUBJECT TO CHANGE

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

GAS
Fixed piping installations
• Check with local gas utility
company or with local codes
for instructions on installing
gas supply lines. All gas
connections should be made
by a competent technician and
in accordance with local codes
and or ordinances. In the
absence of codes, the
installation must comply with
the National Fuel Gas Code
ANSI Z223.1.
• An installer-supplied gas shut-
off valve must be installed in
an easily accessible location.
All installer-supplied parts
must conform to local codes.
• Must be isolated from the gas
supply piping system by closing
its individual manual shut-off
valve during any pressure
testing of that system at test
pressures equal to or less than
1/2 psi (3.5 kPa).
Natural gas models
Water column pressure
o Operating pressure—4.0"
WCP
o Supply pressure of 6" – 10"
WCP
o If incoming pressure exceeds
10" WCP, a step-down
regulator is required.
Accepts standard residential
1/2” (1.3 cm) ID gas service
line; 1/2” (1.3 cm) NPT male
with 7/8” (2.2 cm) flare adapter.
o If using a Viking GSH12
flexible hose, remove the
1/2” (1.3 cm) flare adapter
and attach hose to the 7/8”
(2.2 cm) male flare on the
regulator assembly.
LP/propane models
Water column pressure
o Operating pressure—
10” WCP
o Supply pressure of 11” – 14”
WCP (for fixed piping
installations)
o If incoming pressure exceeds
14” WCP, a step-down
regulator is required.
Accepts standard residential
1/2” (1.3 cm) ID gas service
line; 1/2” (1.3 cm) NPT male
with 3/8” (0.95) flare adapter.
LP/propane tank installations
Water column pressure
o Operating pressure—
10” WCP
Includes high-capacity
hose/regulator assembly for
connection to a standard 5-
gal./20-lb. (approx. 12”
diameter/18”H.) LP/propane
gas cylinder equipped with a
Type 1, QCC-1 connector
o The cylinder connection
device must be compatible
with the Type 1, QCC-1
connector on the outdoor
cooking appliance.
o The cylinder must be
provided with a shut-off valve
terminating in an LP/propane
gas supply cylinder valve
outlet specified.
o The cylinder supply system
must be arranged for vapor
withdrawal and provided
with a listed OPD (overfilling
prevention device).
ELECTRICAL
T-Series models
o 9-volt DC battery for
electronic ignition
o Rotisserie motor max. amp
usage—6.0
E-Series models
o 3’ (91.4 cm) power cord
supply cord with 3-prong
grounded plug attached to
grill
120 VAC/60 Hz
o Grill max. amp usage
VGBQ300—2.1
o 2’ (61.0 cm) power cord supply
cord with 3-prong grounded
plug attached to rotisserie
motor.
120 VAC/60 Hz
o Rotisserie motor max. amp
usage—6.0
PLUMBING
Not applicable
PLANNING AND DESIGN GUIDE
VIKINGRANGE.COM
1-888-VIKING1
OUTDOOR—COOKING
30”W. Ultra-Premium T-Series/E-Series Gas Grill
UTILITY
REQUIREMENTS
Installation Requirements
VGBQ300-2RT/E2
Surface burner rating
Standard SS grill burners (each)
25,000 BTU (7.3 kW) Nat./22,500 BTU (6.5 kW) LP (T-Series)
29,000 BTU (7.3 kW) Nat./28,000 BTU (6.5 kW) LP (E-Series)
Gourmet-Glo™ rotisserie burner
15,000 BTU (4.4 kW) Nat./13,500 BTU (4.0 kW) LP
VGBQ300-2RT2
Ultra-Premium T-Series
Two-Burner Grill
VGBQ300-2RE2
Ultra-Premium E-Series
Two-Burner Grill
REVISED 5/16/11
©2011 VRC—INFORMATION SUBJECT TO CHANGE