Danby DPAC120068 Owners Manual - Page 8

location,making

Page 8 highlights

Window / Patio Door Kit Installation (Air Conditioning Mode ONLY) Your window kit has been designed to fit most standard "vertical" / "horizontal" windows and patio doors up to a maximum height of 80". For vertical window and/or patio door applications, lock positions are provided on thefornt of each slider section. Wing nuts are provided (on the slider sect i on) to secure the section together. Fig. 5a. Horizontal Window • Window Slider Kit Minimum: 28" (71.1 cm) Maximum: 48 (123 cm) a + Fig. 3 Rain Hood Assembly 1) Fold both sides of the Rain Hood 90° as so the flanges are facing outward. Fig 1 Fig. 3a Rain hood inserts are installed in "A" and "B" postions with vent opening facing down (C) 2) Slide the Rain Hood flanges onto the edges of the slider kit until it is lined up with the intake vent (shown in Fig 2). Once the mounting holes on the slider, as well as the Rain Hood are aligned, secure the Rain Hood to the slider with the four mounting screws provided. 4 Vertical Wind Rain Hoodis to be installed only over air intake vent N Rain Hood Slider kit Window Slider Kit Minimum: 28" (71.1 cm) Maximum: 48 3/8" (123 cm) Fig. 2 Intake hose adapter IMPORTANT: • For horizontal window kit applications refer to figure 3a for correct Rain Hood insert positioning. • For vertical window kit applications (includingpatio) refer to figure 4a for correct Rain Hood insert positioning. 1) Select a suitable location,making sure you have access to an electrical outlet. 2) Install both flexible hoses to the rear side of the unit. Both hoses are identical and can be installed into either opening. Insert the hose collar with the 2 lock tabs into the 2 slots on the top of each opening and twist to lock into position. 3) Install the adjustable Window/Patio Door Slider Kit as required. Fig's. 3, 4, 5. Rain hood inserts are installed in "A" and "C" positions with vent opening facing down (B) Fig.4a Please Note: In a vertical application, the exhaust hose MUST be positioned above the intake hose in the window slider. See Fig 5. This will avoid having the exhaust heat go through the intake and back into the unit. Patio Door 4) Install the window exhaust adapters into the openings in the slider section, making sure the window slider sections are secure. Important:: Ensure the exhaust adapter labeled "air intake" is installed on the hose that is connected to the air intake opening on the back of the unit. 7 fig. 5a Fig. 5 Air exhaust Air intake Patio Door Kit Minimum: 28" (67.5 cm) Maximum: 80" (203 cm) Plug the unit into a 115 V / 60 Hz grounded electrical outlet.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22

Window
/
Patio
Door
Kit
Installation
(Air
Conditioning
Mode
ONLY)
Your
window
kit
has
been
designed
to
fit
most
standard
"vertical"
/
"horizontal"
windows
and
patio
doors
up
to
a
maximum
height
of
80".
For
vertical
window
and/or
patio
door
applications,
lock
positions
are
provided
on
thefornt
of
each
slider
section.
Wing
nuts
are
provided
(on
the
slider
sect
i
on)
to
secure
the
section
together.
Fig.
5a.
Rain
Hood
Assembly
1)
Fold
both
sides
of
the
Rain
Hood
90°
as
so
the
fl
anges
are
facing
outward.
Fig
1
2)
Slide
the
Rain
Hood
fl
anges
onto
the
edges
of
the
slider
kit
until
it
is
lined
up
with
the
intake
vent
(shown
in
Fig
2).
Once
the
mounting
holes
on
the
slider,
as
well
as
the
Rain
Hood
are
aligned,
secure
the
Rain
Hood
to
the
slider with
the
four
mounting
screws
provided.
Rain
Hood
is
to
be
installed
only
over
air
intake
vent
Rain
Hood
Fig.
2
Slider
kit
Intake
hose
adapter
IMPORTANT:
For
horizontal
window
kit
applications
refer
to
figure
3a
for
correct
Rain
Hood
insert
positioning.
For
vertical
window
kit
applications
(including
patio)
refer
to
figure
4a
for
correct
Rain
Hood
insert
positioning.
1)
Select
a
suitable
location,making
sure
you
have
access
to
an
electrical
outlet.
2)
Install
both
fl
exible
hoses
to
the
rear
side
of
the
unit.
Both
hoses
are
identical
and
can
be
installed
into
either
opening.
Insert
the
hose
collar
with
the
2
lock
tabs
into
the
2
slots
on
the
top
of
each
opening
and
twist
to
lock
into
position.
3)
Install
the
adjustable
Window/Patio
Door
Slider
Kit
as
required.
Fig's.
3,
4,
5.
4)
Install
the
window
exhaust
adapters
into
the
openings
in
the
slider
section,
making
sure
the
window
slider
sections
are
secure.
Important::
Ensure
the
exhaust
adapter
labeled
"air
intake"
is
installed
on
the
hose
that
is
connected
to
the
air
intake
opening
on
the
back
of
the
unit.
Horizontal
Window
Window
Slider
Kit
Minimum:
28"
(71.1
cm)
Maximum:
48
(123
cm)
a
+
Fig.
3
Fig.
3a
Rain
hood
inserts
are
installed
in
"A"
and
"B"
postions
with
vent
opening
facing
down
(C)
4
Vertical
Wind
N
Window
Slider
Kit
Minimum:
28"
(71.1
cm)
Maximum:
48
3
/
8
"
(123
cm)
Rain
hood
inserts
are
installed
in
"A"
and
"C"
positions
with
vent
opening
facing
down
(B)
Fig.4a
Please
Note:
In
a
vertical
application,
the
exhaust
hose
MUST
be
positioned
above
the
intake
hose
in
the
window
slider.
See
Fig
5.
This
will
avoid
having
the
exhaust
heat
go
through
the
intake
and
back
into
the
unit.
Patio
Door
Fig.
5
Air
exhaust
Air
intake
fig.
5a
Patio
Door
Kit
Minimum:
28"
(67.5
cm)
Maximum:
80"
(203
cm)
Plug
the
unit
into
a
115
V
/
60
Hz
grounded
7
electrical
outlet.