Dell Force10 Z9000 Dell Force10 Z9000 System Quick Start Guide - Page 9

Install the QSFP+ Optics, The Z9000 has 32 QSFP+ optical ports. For supported optics, refer - specifications

Page 9 highlights

NOTE: Coat the one-hole lug with an anti-oxidant compound prior to crimping. Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant prior to mating. Plated mating surfaces must be clean and free from contamination. Step Task 1 Take the (1) M4x0.7 screw from the package. 2 Cut cable to desired length. Cable length must facilitate the proper operation of fault interrupt circuits. Dell Force10 recommends using the shortest cable route allowable. 3 Attach the one-hole lug to the chassis as shown, using the supplied screw with captive internal tooth lock washer. The screw should be torqued to 20 in-lbs. Grounding point 40G/4x10G QSFP+ ports 4 Attach the other end of the ground cable to a suitable ground point. The rack installation ears are not a suitable grounding point. Install the QSFP+ Optics The Z9000 has 32 QSFP+ optical ports. For supported optics, refer to http://www.force10networks.com/products/specifications.asp. CAUTION: Electrostatic discharge (ESD) damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the Z9000 and its components. WARNING: Follow all warning labels when working with optical fibers. Always wear eye protection when working with optical fibers. Never look directly into the end of a terminated or unterminated fiber or connector as it may cause eye damage. Step Task 1 Position the optic so it is in the correct position. (The optic has a key that prevents it from being inserted incorrectly. Installing the Hardware 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

Installing the Hardware
7
NOTE:
Coat the one-hole lug with an anti-oxidant compound prior to crimping.
Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant
prior to mating. Plated mating surfaces must be clean and free from contamination.
Install the QSFP+ Optics
The Z9000 has 32 QSFP+ optical ports. For supported optics, refer to
CAUTION: Electrostatic discharge (ESD) damage can occur if components
are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the Z9000 and its components.
WARNING: Follow all warning labels when working with optical fibers.
Always wear eye protection when working with optical fibers. Never look
directly into the end of a terminated or unterminated fiber or connector as it
may cause eye damage.
Step
Task
1
Take the (1) M4x0.7 screw from the package.
2
Cut cable to desired length. Cable length must facilitate the proper
operation of fault interrupt circuits. Dell Force10 recommends using the
shortest cable route allowable.
3
Attach the one-hole lug to the chassis as shown, using the supplied
screw with captive internal tooth lock washer. The screw should be
torqued to 20 in-lbs.
4
Attach the other end of the ground cable to a suitable ground point. The
rack installation ears are not a suitable grounding point.
Step
Task
1
Position the optic so it is in the correct position. (The optic has a key that
prevents it from being inserted incorrectly.
40G/4x10G
QSFP+ ports
Grounding
point