Dell PowerEdge 2650 Cabling Instructions for the –48 VDC - Page 6
Assembling the Safety Ground Wire
View all Dell PowerEdge 2650 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 6 highlights
www.dell.com | support.dell.com Assembling the Safety Ground Wire 1 Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm (0.175 inches) of copper wire. 2 Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire. Connecting the -48 VDC Power Cable and Safety Ground 1 Connect the safety ground to the grounding post on the back of the system using a #6-32 nut equipped with a locking washer (see Figure 1-2). 2 Plug the DC power cable into the system. Figure 1-2. Safety Ground safety ground grounding post lock washer #6-32 nut 1-4 Cabling Instructions for the -48 VDC
1-4
Cabling Instructions for the °48 VDC
www.dell.com | support.dell.com
Assembling the Safety Ground Wire
1
Strip the insulation from the end of the green/yellow wire, exposing approximately
4.5 mm (0.175 inches) of copper wire.
2
Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire.
Connecting the °48 VDC Power Cable and
Safety Ground
1
Connect the safety ground to the grounding post on the back of the system using a
#6-32 nut equipped with a locking washer (see Figure 1-2).
2
Plug the DC power cable into the system.
Figure 1-2.
Safety Ground
safety ground
grounding post
lock washer
#6-32 nut