RA 4-Pole Measurements, function. See
View all Fluke 1623-2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
Earth/Ground Tester Operation RA 4-Pole Measurements To make 4-pole measurements: 1. Select 4 POLE function. See Figure 5. 2. Connect test leads. Connect terminals E/C1 and ES/P1 to the earth system to be measured with the two supplied test leads (1.5 m). Place two ground stakes in earth/dirt. Minimum distance between earth electrode (E/C1), probe (S/P2), and auxiliary earth (H/C2) should be at least 20 m. The ES test lead eliminates the influence of the test leads. Connect the stakes with the 25 m and 50 m cable reels to H/C2 and S/P2 as shown below. 3. Push START. indicates that a measurement is in progress. For a continuous measurement, continue to push the START button. 4. indicates a completed measurement. The result is kept on the display until a new measurement is started or the rotary switch is turned. 13 MyFlukeStore Shop for Fluke products online at: www. .com 1.877.766.5412