Fluke 1623-2 Manual - Page 33
ER Ea
View all Fluke 1623-2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 33 highlights
Earth/Ground Tester Advanced Operation From the indicated resistance value RE, the soil resistivity calculates according to the equation: ρ E = 2π .a.RE ρE ...... mean value of soil resistivity (Ωm) RE ...... measured resistance (Ω) a ...... probe distance (m) The measuring method according to Wenner determines the soil resistivity down to a depth of approx. the distance "a" between two earth stakes. By increasing "a", deeper strata can be measured and checked for homogeneity. By changing "a" several times, a profile can be measured from which a suitable earth electrode can be determined. According to the depth to be measured, "a" is selected between 2 m and 30 m. This procedure results in curves depicted in the graph below. 1 3 2 Soil restivity ρE Curve 1: Curve 2: A Distances of Probe edw021.eps As ρE decreases only deeper down, a deep earth electrode is advisable As ρE decreases only down to point A, an increase in the depth deeper than A does not improve the values. 25 MyFlukeStore Shop for Fluke products online at: www. .com 1.877.766.5412