Fluke 1623-2 Manual - Page 23
RA 3-Pole Selective Earth Resistance Measurement with Current Clamp, See
View all Fluke 1623-2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Earth/Ground Tester Operation RA 3-Pole Selective Earth Resistance Measurement with Current Clamp The RA 3-pole Selective Earth Resistance Measurement with Current Clamp procedure is useful for the resistance measurement of different parallel sections of an earth/ground system. 1. Select 3 POLE . See Figure 6. 2. Connect test leads. Connect the supplied test lead (1.5 m) to terminal E/C1 and its other end to the ground system to be measured. Place two ground stakes in earth/dirt. Minimum distance between earth electrode (E/C1), probe (S/P2) and auxiliary earth (H/C2) should be at least 20 m. Connect stakes with 25 m and 50 m wires to H/C2 and S/P2 as shown. Connect current clamp with adapter cable as shown. 3. Push START. indicates that measurement is in progress. For continuous measurement, continue to push the START button. 4. indicates completed measurement. The result is kept on display until a new measurement is started or the rotary switch is turned. 15 MyFlukeStore Shop for Fluke products online at: www. .com 1.877.766.5412