Gateway 9510 Gateway 9510 Server User Guide - Page 97
Replacing a hot-swap fan
View all Gateway 9510 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 97 highlights
Chapter 4: Installing Components Replacing a hot-swap fan If you are adding redundant hot-swap fans to your server, you must update the FRU/SDR. For more information, see "Updating the FRU/SDR" on page 37. Important Make sure that you replace a fan with an identical replacement fan. To replace a hot-swap fan: 1 Follow the instructions in "Preventing static electricity discharge" on page 41. 2 Follow the instructions in "Opening the server case" on page 42. 3 While pressing the locking clip, slide the fan out of the case. Fan locking clip 4 Insert the new fan into the fan slot until it snaps into place. 5 Follow the instructions in "Closing the server case" on page 52. 92 www.gateway.com
92
www.gateway.com
Chapter 4: Installing Components
Replacing a hot-swap fan
If you are adding redundant hot-swap fans to your server, you must update the FRU/SDR.
For more information, see
“Updating the FRU/SDR” on page 37
.
To replace a hot-swap fan:
1
Follow the instructions in
“Preventing static electricity discharge” on page 41
.
2
Follow the instructions in
“Opening the server case” on page 42
.
3
While pressing the locking clip, slide the fan out of the case.
4
Insert the new fan into the fan slot until it snaps into place.
5
Follow the instructions in
“Closing the server case” on page 52
.
Important
Make sure that you replace a fan with an identical replacement fan.
Fan locking clip