Haier AB12CS1ERA Service Manual - Page 20
AD24LS1ERA
View all Haier AB12CS1ERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
>_]]VbTZR\ _^UZdZ_^Vb Item Model Function Capacity kW Sensible heat ratio Dehumidifying capacity 10‐³×m³/h Power Supply Type × Number Fan Speed(H-M-L) Fan motor output power r/min kW Air-flow(H-M-L) m³/h Static pressure Pa Indoor unit Type / Diameter mm Heat exchanger Total Area m² Temp. scope ℃ Dimension External Package (L×W×H) (L×W×H) mm×mm×mm mm×mm×mm Drainage pipe (material , I.D./O.D.) mm Control type (Remote /wired) Noise level (H-M-L) dB(A) Weight (Net / Shipping) kg / kg Refrigerant Type PIPING Pipe Liquid Gas mm mm Connecting Method AD24LS1ERA cooling 6.8(2.0---7.6) heating 7.1(3.0---8.3) 0.72 / 2.2 1PH,220-230VAC,50HZ centrifugal*2 1250±40/1130±40/1000±50/850±50 0.05 1200/1050/850(white terminal 0 Pa) 25 inner grooved pipe/φ7 0.51 2-7 1090*500*220 1174*549*294 20/24 wired, YR-E14 49/45/41/37 25.2/28.4 R410A 9.52 15.88 flared Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level. -20-