HP 418800-B21 HP StorageWorks MSA60/70 Storage Enclosure Firmware Release Note - Page 9

Binary file installation instructions using FTP

Page 9 highlights

Binary file installation instructions using FTP NOTE: It takes approximately 10 minutes for the firmware to load and for the automatic restart to complete. Progress messages are displayed in the FTP interface during that time. Wait for the progress messages to specify that the firmware load has completed. If the system Partner Firmware Update (PFU) option is enabled, allow an additional 20 minutes for the partner controller to be updated. No messages are displayed in the FTP interface during PFU. 1. Download the firmware file to your computer or network. 2. Prepare to use FTP: a. Determine the network-port IP addresses of the system controllers. b. Verify that the system FTP service is enabled. c. Verify that the user you will log in as has permission to use the FTP interface and has manage access rights. d. Secure the IOM addresses to be loaded in the format : (for example 0:15 or 1:31). TIP: For MSA70 connected to an MSA2000 G2 or P2000 G3 array controller enclosure, in the SMU, the EMP addresses are displayed by clicking each enclosure in the Configuration View. The needed data is displayed in the fields labeled EMP A Bus ID, EMP B Bus ID, EMP A Target ID, EMP B Target ID, EMP A Revision, and EMP B Revision. (The terms bus and channel are equivalent.) In the CLI, enter show enclosures. The needed data is displayed in the columns labeled EMP A CH:ID Rev and EMP B CH:ID Rev. There are typically IOMs in each 3.5 inch drive enclosure. 3. Open a command prompt (Windows) or a terminal window (UNIX), and navigate to the directory containing the firmware file to load. a. Enter ftp For example: ftp 10.1.0.9 b. Log in as an FTP user (user = ftp, password = flash). c. Enter put encl:: flash nl For example: put O300B23.bin encl:1:31 flash Effective date February 2010 HP StorageWorks MSA60/70 Storage Enclosure Firmware Release Notes 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10

Binary file installation instructions using FTP
NOTE:
It takes approximately 10 minutes for the firmware to load and for the automatic restart to complete.
Progress messages are displayed in the FTP interface during that time. Wait for the progress messages
to specify that the firmware load has completed. If the system Partner Firmware Update (PFU) option
is enabled, allow an additional 20 minutes for the partner controller to be updated. No messages
are displayed in the FTP interface during PFU.
1.
Download the firmware file to your computer or network.
2.
Prepare to use FTP:
a.
Determine the network-port IP addresses of the system controllers.
b.
Verify that the system FTP service is enabled.
c.
Verify that the user you will log in as has permission to use the FTP interface and has manage
access rights.
d.
Secure the IOM addresses to be loaded in the format <channel-ID>:<EMP-number> (for
example 0:15 or 1:31).
TIP:
For MSA70 connected to an MSA2000 G2 or P2000 G3 array controller enclosure,
in the SMU, the EMP addresses are displayed by clicking each enclosure in the
Configuration View. The needed data is displayed in the fields labeled
EMP A Bus ID
,
EMP B Bus ID
,
EMP A Target ID
,
EMP B Target ID
,
EMP A Revision
, and
EMP B Revision
.
(The terms
bus
and
channel
are equivalent.)
In the CLI, enter
show enclosures
. The needed data is displayed in the columns
labeled
EMP A CH:ID Rev
and
EMP B CH:ID Rev
.
There are typically IOMs in each 3.5 inch drive enclosure.
3.
Open a command prompt (Windows) or a terminal window (UNIX), and navigate to the directory
containing the firmware file to load.
a.
Enter
ftp <controller-network-address>
For example:
ftp 10.1.0.9
b.
Log in as an FTP user (user =
ftp
, password =
flash
).
c.
Enter
put <firmware-file> encl:<channel-ID>:<EMP-number> flash
nl
For example:
put O300B23.bin encl:1:31 flash
Effective date
February 2010
HP StorageWorks MSA60/70 Storage Enclosure Firmware Release Notes