HP ProLiant BL280c HP Power Advisor utility: a tool for estimating power requi - Page 14
amperes total current 20 x 2.38 A drawn by the 24 servers
View all HP ProLiant BL280c manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
Figure 12. Power calculation for 20 HP DL380 G6 servers The Power Advisor determines that a rack configuration of 20 DL380 G6 servers would require the following: • 5761.6 VA total apparent power (20 x 288.08 VA) that the power distribution components must transfer • 17887.2 total BTU/hr that will need to be removed by the cooling system • 27.6 amperes total current (20 x 2.38 A) drawn by the 24 servers • 5245 total watts dissipated by the equipment 14
Figure 12.
Power calculation for 20 HP DL380 G6 servers
The Power Advisor determines that a rack configuration of 20 DL380 G6 servers would require the
following:
•
5761.6 VA total apparent power (20 x 288.08 VA) that the power distribution components must
transfer
•
17887.2 total BTU/hr that will need to be removed by the cooling system
•
27.6 amperes total current (20 x 2.38 A) drawn by the 24 servers
•
5245 total watts dissipated by the equipment
14