HP ProLiant BL280c HP Power Advisor utility: a tool for estimating power requi - Page 14

amperes total current 20 x 2.38 A drawn by the 24 servers

Page 14 highlights

Figure 12. Power calculation for 20 HP DL380 G6 servers The Power Advisor determines that a rack configuration of 20 DL380 G6 servers would require the following: • 5761.6 VA total apparent power (20 x 288.08 VA) that the power distribution components must transfer • 17887.2 total BTU/hr that will need to be removed by the cooling system • 27.6 amperes total current (20 x 2.38 A) drawn by the 24 servers • 5245 total watts dissipated by the equipment 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22

Figure 12.
Power calculation for 20 HP DL380 G6 servers
The Power Advisor determines that a rack configuration of 20 DL380 G6 servers would require the
following:
5761.6 VA total apparent power (20 x 288.08 VA) that the power distribution components must
transfer
17887.2 total BTU/hr that will need to be removed by the cooling system
27.6 amperes total current (20 x 2.38 A) drawn by the 24 servers
5245 total watts dissipated by the equipment
14