HP ProLiant SL270s HP ProLiant SL Servers Planning Guide - Page 28

Raised floor \, If a bolted-stringer raised floor system is not used

Page 28 highlights

Power panels located in close proximity to the computer equipment should also be connected to the site grounding grid. Raised floor "high-frequency noise" grounding IMPORTANT: Regardless of the grounding connection method used, the raised floor should be grounded as an absolute safety minimum. If a raised floor system is used, the floor must be designed as a signal ground grid that maintains an equal potential over a broad band of frequencies. To accomplish this, observe the following guidelines: • Use a raised floor system where the stringers are bolted to the pedestals. • Select floor components that have a corrosion-resistant plating to provide low resistance connection points to other components and to computer cabinets. • Connect a 2/0 copper conductor to every other pedestal around the perimeter and to the equipment grounding system of the building. • Bond all metal pipes that enter or leave the raised floor area to the 2/0 perimeter ground. • Bond each row and column of the floor grid to the 2/0 perimeter ground. • Bond any I-beams that penetrate the raised floor to the pedestals. • Connect the opposite corners of equipment cabinets to the pedestals with #12 stranded wire. • Where the cabinets are bolted together in rows, bonding two corners at opposite ends of the row is sufficient. • Bonding straps should be 70 cm (24 in) or less in length. If a bolted-stringer raised floor system is not used, the alternate methods that may provide acceptable results include the following: • Use a grounded #6 AWG minimum copper wire grid that is clamped mechanically to floor pedestals and bonded properly to the building or site ground. • Add a grounding grid made of copper strips mounted to the subfloor. The strips should be 0.8 mm (0.032 in) thick and a minimum of 76 mm (3.0 in) wide. Connect each pedestal to four strips using 6-mm (0.25-in) bolts tightened to the manufacturer's torque recommendation. Power requirements and considerations 28

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

Power requirements and considerations
28
Power panels located in close proximity to the computer equipment should also be connected to the site
grounding grid.
Raised floor "high-frequency noise" grounding
IMPORTANT:
Regardless of the grounding connection method used, the raised floor should be
grounded as an absolute safety minimum.
If a raised floor system is used, the floor must be designed as a signal ground grid that maintains an equal
potential over a broad band of frequencies. To accomplish this, observe the following guidelines:
Use a raised floor system where the stringers are bolted to the pedestals.
Select floor components that have a corrosion-resistant plating to provide low resistance connection
points to other components and to computer cabinets.
Connect a 2/0 copper conductor to every other pedestal around the perimeter and to the equipment
grounding system of the building.
Bond all metal pipes that enter or leave the raised floor area to the 2/0 perimeter ground.
Bond each row and column of the floor grid to the 2/0 perimeter ground.
Bond any I-beams that penetrate the raised floor to the pedestals.
Connect the opposite corners of equipment cabinets to the pedestals with #12 stranded wire.
Where the cabinets are bolted together in rows, bonding two corners at opposite ends of the row is
sufficient.
Bonding straps should be 70 cm (24 in) or less in length.
If a bolted-stringer raised floor system is not used, the alternate methods that may provide acceptable results
include the following:
Use a grounded #6 AWG minimum copper wire grid that is clamped mechanically to floor pedestals
and bonded properly to the building or site ground.
Add a grounding grid made of copper strips mounted to the subfloor. The strips should be 0.8 mm
(0.032 in) thick and a minimum of 76 mm (3.0 in) wide. Connect each pedestal to four strips using
6-mm (0.25-in) bolts tightened to the manufacturer’s torque recommendation.