Environmental requirements Environmental elements The following environmental elements can affect HP ProLiant SL server product installation. Humidity level Maintaining proper humidity levels in the computer room is essential for reliable equipment performance. Humidity levels outside the recommended range of 25% to 45%, especially if these levels are sustained, lead to equipment damage and result in equipment malfunction through several mechanisms. High humidity levels enable galvanic activity to occur between dissimilar metals. Galvanic activity can cause high resistance to develop between connections and lead to equipment malfunctions and failures. Extended periods of humidity levels greater than 60% have also been shown to adversely affect modern printed circuit board reliability. High humidity can also adversely affect some magnetic tapes and paper media. High humidity levels are often the result of malfunctioning facility air conditioning systems. High humidity can also be the result of facility expansion in excess of air conditioning system capacity. Humidity levels below the minimum recommended value can also have undesirable effects. Low humidity contributes to high ESD voltage potentials. ESD events can cause component damage during service operations and equipment malfunction or damage during normal operation. Low humidity levels can reduce the effectiveness of static dissipating materials and have also been shown to cause high speed printer paper feed problems. Low humidity levels are often the result of the facility heating system and occur during the cold season. Most heating systems cause air to have a low humidity level, unless the system has a built-in humidifier. ASHRAE and representatives of IT equipment manufacturers recommend a range of 18°C dry bulb with a 5.5°C dew point temperature to 27°C dry bulb with a 5.5°C dew point temperature. Over this range of dry bulb temperature with a 5.5°C dew point, the relative humidity varies from approximately 25% to 45%. For more information on humidity levels, see the ASHRAE website (http://www.ashrae.org). Dust and pollution Dust and microscopic particles in the site environment adversely affect computer equipment. Airborne abrasive particles can cause bearing failures in disk drives, tape drives, and other mechanical devices. Dust may also blanket electronic components and printed circuit boards, causing premature failure because of excess heat, humidity buildup, or both. Conductive metallic particles can cause power supply and other electronic component failures. A build-up of these metallic particles over time can cause short circuits on the densely packed circuit boards common in modern electronics. Use every effort to ensure that the environment is as dust- and particulate-free as possible. See "Metallic particulate contamination (on page 8)." Environmental requirements 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

Environmental requirements 7
Environmental requirements
Environmental elements
The following environmental elements can affect HP ProLiant SL server product installation.
Humidity level
Maintaining proper humidity levels in the computer room is essential for reliable equipment performance.
Humidity levels outside the recommended range of 25% to 45%, especially if these levels are sustained, lead
to equipment damage and result in equipment malfunction through several mechanisms.
High humidity levels enable galvanic activity to occur between dissimilar metals. Galvanic activity can cause
high resistance to develop between connections and lead to equipment malfunctions and failures. Extended
periods of humidity levels greater than 60% have also been shown to adversely affect modern printed circuit
board reliability. High humidity can also adversely affect some magnetic tapes and paper media.
High humidity levels are often the result of malfunctioning facility air conditioning systems. High humidity can
also be the result of facility expansion in excess of air conditioning system capacity.
Humidity levels below the minimum recommended value can also have undesirable effects. Low humidity
contributes to high ESD voltage potentials. ESD events can cause component damage during service
operations and equipment malfunction or damage during normal operation. Low humidity levels can reduce
the effectiveness of static dissipating materials and have also been shown to cause high speed printer paper
feed problems.
Low humidity levels are often the result of the facility heating system and occur during the cold season. Most
heating systems cause air to have a low humidity level, unless the system has a built-in humidifier.
ASHRAE and representatives of IT equipment manufacturers recommend a range of 18°C dry bulb with a
5.5°C dew point temperature to 27°C dry bulb with a 5.5°C dew point temperature. Over this range of dry
bulb temperature with a 5.5°C dew point, the relative humidity varies from approximately 25% to 45%.
For more information on humidity levels, see the ASHRAE website (
).
Dust and pollution
Dust and microscopic particles in the site environment adversely affect computer equipment. Airborne
abrasive particles can cause bearing failures in disk drives, tape drives, and other mechanical devices. Dust
may also blanket electronic components and printed circuit boards, causing premature failure because of
excess heat, humidity buildup, or both.
Conductive metallic particles can cause power supply and other electronic component failures. A build-up of
these metallic particles over time can cause short circuits on the densely packed circuit boards common in
modern electronics. Use every effort to ensure that the environment is as dust- and particulate-free as possible.
See "Metallic particulate contamination (on page
8
)."