Specifications Power requirements and considerations When calculating power for the scalable system, be sure to include power for network switches, UPS devices, and other options. To supply adequate power to the scalable system, observe the power input requirements for each type of server power supply, and then provide the sufficient number of PDUs and distribution cables or devices. Specification Rated input voltage Rated input frequency Rated input current Rated input power (AC input) Btus per hour (AC input) 750 W power supply 100 to 120 VAC 200 to 240 VAC 50 Hz to 60 Hz 8.9 A at 100 VAC 4.3 A at 200 VAC 857 W at 100 V 824 W at 200 V 2925 at 120 V 2812 at 200 V to 240 V 1200 W power supply 100 to 120 VAC 200 to 240 VAC 50 Hz to 60 Hz 10 A at 100 VAC 4.9 A at 200 VAC 930 W at 100 V 1348 W at 200 V 3530 at 120 V 4600 at 200 V to 240 V Environmental specifications Specification Value Temperature range* Operating Shipping Maximum wet bulb temperature Relative humidity (noncondensing)** Operating Nonoperating 10°C to 35°C (50°F to 95°F) -40°C to 70°C (-40°F to 158°F) 28°C (82.4°F) 10% to 90% 5% to 95% * All temperature ratings shown are for sea level. An altitude derating of 1°C per 300 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. ** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage corresponds to a pressure minimum of 70 kPa. Hot-plug power supply calculations For hot-plug power supply specifications and calculators to determine electrical and heat loading for the server, refer to the HP Enterprise Configurator website (http://h30099.www3.hp.com/configurator/). Specifications 27

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30

Specifications 27
Specifications
Power requirements and considerations
When calculating power for the scalable system, be sure to include power for network switches, UPS
devices, and other options.
To supply adequate power to the scalable system, observe the power input requirements for each type of
server power supply, and then provide the sufficient number of PDUs and distribution cables or devices.
Specification
750 W power supply
1200 W power supply
Rated input voltage
100 to 120 VAC
200 to 240 VAC
100 to 120 VAC
200 to 240 VAC
Rated input frequency
50 Hz to 60 Hz
50 Hz to 60 Hz
Rated input current
8.9 A at 100 VAC
4.3 A at 200 VAC
10 A at 100 VAC
4.9 A at 200 VAC
Rated input power
(AC input)
857 W at 100 V
824 W at 200 V
930 W at 100 V
1348 W at 200 V
Btus per hour
(AC input)
2925 at 120 V
2812 at 200 V to 240 V
3530 at 120 V
4600 at 200 V to 240 V
Environmental specifications
Specification
Value
Temperature range*
Operating
10
°
C to 35
°
C (50
°
F to 95
°
F)
Shipping
-40
°
C to 70
°
C (-40
°
F to 158
°
F)
Maximum wet bulb temperature
28
°
C (82.4
°
F)
Relative humidity
(noncondensing)**
Operating
10% to 90%
Nonoperating
5% to 95%
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 300 m (1.8°F per 1,000 ft) to 3,048
m (10,000 ft) is applicable. No direct sunlight allowed.
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for
storage corresponds to a pressure minimum of 70 kPa.
Hot-plug power supply calculations
For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, refer to the HP Enterprise Configurator website (
).