HP Surestore Disk System fc10 Hewlett-Packard HP SureStore E Disk System FC10 - Page 102
Compare temperature reported
View all HP Surestore Disk System fc10 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 102 highlights
Problem HWEvent LED Description Category State Temperature Critical is over limit none Major none Warning Temperature Critical is under limit none Major none Warning Voltage is over limit Voltage is under limit Critical none Major none Warning Critical none Major none Warning Status SAM none none none none none none none none STM Probable Cause/Solution Critical Temp is >54.5º C Noncritical Temp is >36º C - A fan is faulty. Check status and correct. - Airflow is obstructed; vents are blocked. - One or more slots are empty. - Power supply is faulty. Check status and correct. - Room temperature is too high. If ambient temperature cannot be reduced in a reasonable time, turn off product to prevent shortened life. - Temperature sensor is faulty. Compare temperature reported by peer LCC. Critical Temps