Honeywell T7351F2010 Installation Instructions - Page 10

Dehumid Hot Gas BP

Page 10 highlights

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Dehumid Hot Gas BP The auxiliary output operates as shown in Table 6. Table 6. Hot Gas Bypass Dehumidification Logic. Humidity Cooling Stages Active Auxiliary Output High more than one De-energized High one or less Energized Low more than one De-energized Low one or less De-energized Auxiliary output during call for multiple cooling stages for two reasons: 1. This method assumes that the cooling provides dehumidification. 2. Multiple cooling stages probably provide necessary dehumidification. 3. Hysteresis and a minimum timer prevent short cycling of this output. 62-0258-05 10

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
62-0258—05
10
Dehumid Hot Gas BP
The auxiliary output operates as shown in Table 6.
Table 6. Hot Gas Bypass Dehumidification Logic.
Auxiliary output during call for multiple cooling stages for
two reasons:
1.
This method assumes that the cooling provides
dehumidification.
2.
Multiple cooling stages probably provide necessary
dehumidification.
3.
Hysteresis and a minimum timer prevent short
cycling of this output.
Humidity
Cooling Stages Active
Auxiliary Output
High
more than one
De-energized
High
one or less
Energized
Low
more than one
De-energized
Low
one or less
De-energized