WIRING DIAGRAMS T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT GND SENSOR SET PT LED BYPASS TR23-H REMOTE SENSOR 1 2 3 4 5 6 7 8 9 10 11 12 OUTDOOR AIR SENSOR DISCHARGE AIR SENSOR COMPRESSOR CONTACTOR 2 AUX HEAT STAGE 1 SUBBASE T5 T6 T7 T4 T3 OS OS AS AS W2 W1 Y2 4 HS HC HP M M X RH RC AUX O/B Y1 G 2 HUMIDITY SENSOR MOTION SENSOR CHANGEOVER FAN RELAY COMPRESSOR 3 CONTACTOR 1 1 L2 L1 (HOT) HEATING TRANSFORMER ECONOMIZER L2 1 L1 (HOT) COOLING TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER. 3 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. 4 WHEN USING THE TR23-H FOR HUMIDITY SENSING, THERE IS NO NEED TO WIRE THE HC TERMINAL BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1 COMMON AT THE SENSOR. M29323 Fig. 7. Typical hookup of T7351F2010 in two-stage heat and two-stage cool heat pump system with two transformers. GND SENSOR SET PT LED BYPASS TR23-H REMOTE SENSOR 1 2 3 4 5 6 7 8 9 10 11 12 OUTDOOR AIR SENSOR HEAT RELAY 2 DISCHARGE AIR SENSOR COMPRESSOR CONTACTOR 4 COMPRESSOR CONTACTOR 2 SUBBASE T5 T6 T7 T4 T3 OS OS AS AS W3/Y4 Y3 W2 Y2 HS HC HP M M X RH RC AUX W1 Y1 G 5 HUMIDITY SENSOR MOTION SENSOR 3 HEAT FAN RELAY 1 RELAY COMPRESSOR CONTACTOR 3 1 2 L2 L1 (HOT) COMPRESSOR CONTACTOR 1 4 ECONOMIZER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD. 3 HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER. 4 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. 5 WHEN USING THE TR23-H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE HC TERMINAL BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1 COMMON AT THE SENSOR. M29254 Fig. 8. Typical hookup of T7351F2010 in two-stage heat and four-stage cool conventional system. 11 62-0258-05

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
11
62-0258—05
WIRING DIAGRAMS
Fig. 7. Typical hookup of T7351F2010 in two-stage heat and two-stage cool heat pump system with two
transformers.
Fig. 8. Typical hookup of T7351F2010 in two-stage heat and four-stage cool conventional system.
POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
WHEN USING THE TR23-H FOR HUMIDITY SENSING, THERE IS NO NEED TO WIRE THE HC TERMINAL
BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1
COMMON AT THE SENSOR.
1
M29323
2
2
3
4
4
RC
X
SUBBASE
O/B
G
Y1
W1
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
DISCHARGE
AIR SENSOR
OUTDOOR
AIR
SENSOR
OS
OS
AS
AS
1
3
L1
(HOT)
L2
1
L1
(HOT)
L2
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
HEATING
TRANSFORMER
COOLING
TRANSFORMER
CHANGE-
OVER
FAN
RELAY
ECONOMIZER
AUX HEAT
STAGE 1
MOTION
SENSOR
HUMIDITY
SENSOR
M
M
HC
HP
HS
TR23-H REMOTE SENSOR
9
8
7
6
5
4
3
2
1
10
11
12
GND
SENSOR
SET PT
LED
BYPASS
POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
WHEN USING THE TR23-H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE HC TERMINAL
BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC, WHICH IS ALSO TIED TO TERMINAL 1
COMMON AT THE SENSOR.
1
M29254
2
3
2
3
4
RC
X
SUBBASE
W1
G
Y1
W3/Y4
Y3
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
DISCHARGE
AIR
SENSOR
OUTDOOR
AIR
SENSOR
MOTION
SENSOR
HUMIDITY
SENSOR
M
OS
OS
AS
AS
M
HC
HP
HS
1
4
L1
(HOT)
L2
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
HEAT
RELAY 1
FAN
RELAY
ECONOMIZER
HEAT
RELAY 2
COMPRESSOR
CONTACTOR 3
COMPRESSOR
CONTACTOR 4
TR23-H REMOTE SENSOR
9
8
7
6
5
4
3
2
1
10
11
12
GND
SENSOR
SET PT
LED
BYPASS
5
5