Honeywell T7351F2010 Installation Instructions - Page 5

Table 3. Installer Setup., Continued, Default, Choices, Notes - remote sensor

Page 5 highlights

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Text Default Choices HEATPMP 0 0 - 2 COOLSTG 1 0 - 4 HEATSTG 1 0 - 3 AUX STG 0 0 - 2 AUX CON 0 0 - 3 WALLMOD 0 0 - 3 OATSENS 0 DATSENS 0 HUMSENS 0 0 - 1 0 - 1 0 - 2 OCCSENS 0 0 - 1 FAN HT 0 0 - 1 XFAN HT YES YES or NO XFAN CL NO YES or NO STRTDEL 0 ADVANCE NO 0 - 15 YES or NO Table 3. Installer Setup. (Continued) Notes Application Type Selection 0: Conventional 1: Heat Pump - Cooling (Energize O/B on call for cool) 2: Heat Pump - Heating (Energize O/B on call for heat) Number of Cooling Stages 0: 0 Stages of Cooling 1: 1 Stages of Cooling 2: 2 Stages of Cooling 3: 3 Stages of Cooling (Not available if Heat Pump is selected) 4: 4 Stages of Cooling (W3 will be used as 4th stage relay) (Not available if Heat Pump is selected) Number of Heating Stages (Not available if Heat Pump is selected) 0: 0 Stages of Heating 1: 1 Stages of Heating 2: 2 Stages of Heating (This is the max if 4 cooling stages is selected) 3: 3 Stages of Heating Number of Heat Pump Heating Stages (Only shown when Heat Pump is selected) 0: 0 Aux Stages 1: 1 Aux Stages 2: 2 Aux Stages Aux Contact Functionality 0: Time of Day 1: Economizer 2: Dehumid - Hot Gas Bypass 3: Simple Dehumid Remote Room Sensor Selection 0: Local sensor only 1: TR21/TR24 and T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0) 2: TR22/TR23 and T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0) 3: T7771 (Remote sensor, Remote Setpoint, Bypass 1) (Bypass 0 means that by pressing the override button the thermostat goes from unoccupied to occupied and the LED will light up and the temporary occupied timer will begin. If the button is pressed again, the timer will restart.) (Bypass 1 means that by pressing the override button a second time the thermostat can return to the unoccupied period.) Outdoor Air Sensor Selection 0: None 1: Remote Outdoor Air Sensor Discharge Air Sensor Selection 0: None 1: Remote Discharge Air Sensor Room Humidity Sensor selection 0: None 1: On Board Sensor 2: Remote Sensor Occupancy Sensor Selection 0: None 1: Remote Occ Sensor Fan Operation on Heat 0: Conventional (Equipment controls Fan) 1: Electric (Thermostat turns on Fan with call for Heat) Extended Fan on Heat NO: None YES: 90 seconds Extended Fan on Cool NO: None YES: 40 seconds Sequential Start Delay 0 to 150 seconds in 10 second increments Advanced Settings NO: Hide YES: Show 5 62-0258-05

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
5
62-0258—05
HEATPMP
0
0 - 2
Application Type Selection
0: Conventional
1: Heat Pump - Cooling (Energize O/B on call for cool)
2: Heat Pump - Heating (Energize O/B on call for heat)
COOLSTG
1
0 - 4
Number of Cooling Stages
0: 0 Stages of Cooling
1: 1 Stages of Cooling
2: 2 Stages of Cooling
3: 3 Stages of Cooling
(Not available if Heat Pump is selected)
4: 4 Stages of Cooling (W3 will be used as 4th stage relay) (Not available if Heat
Pump is selected)
HEATSTG
1
0 - 3
Number of Heating Stages (Not available if Heat Pump is selected)
0: 0 Stages of Heating
1: 1 Stages of Heating
2: 2 Stages of Heating (This is the max if 4 cooling stages is selected)
3: 3 Stages of Heating
AUX STG
0
0 - 2
Number of Heat Pump Heating Stages (Only shown when Heat Pump is
selected)
0: 0 Aux Stages
1: 1 Aux Stages
2: 2 Aux Stages
AUX CON
0
0 - 3
Aux Contact Functionality
0: Time of Day
1: Economizer
2: Dehumid - Hot Gas Bypass
3: Simple Dehumid
WALLMOD
0
0 - 3
Remote Room Sensor Selection
0: Local sensor only
1: TR21/TR24 and T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0)
2: TR22/TR23 and T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0)
3: T7771 (Remote sensor, Remote Setpoint, Bypass 1)
(Bypass 0 means that by pressing the override button the thermostat goes from
unoccupied to occupied and the LED will light up and the temporary occupied
timer will begin. If the button is pressed again, the timer will restart.)
(Bypass 1 means that by pressing the override button a second time the
thermostat can return to the unoccupied period.)
OATSENS
0
0 - 1
Outdoor Air Sensor Selection
0: None
1: Remote Outdoor Air Sensor
DATSENS
0
0 - 1
Discharge Air Sensor Selection
0: None
1: Remote Discharge Air Sensor
HUMSENS
0
0 - 2
Room Humidity Sensor selection
0: None
1: On Board Sensor
2: Remote Sensor
OCCSENS
0
0 - 1
Occupancy Sensor Selection
0: None
1: Remote Occ Sensor
FAN HT
0
0 - 1
Fan Operation on Heat
0: Conventional (Equipment controls Fan)
1: Electric (Thermostat turns on Fan with call for Heat)
XFAN HT
YES
YES or NO
Extended Fan on Heat
NO: None
YES: 90 seconds
XFAN CL
NO
YES or NO
Extended Fan on Cool
NO: None
YES: 40 seconds
STRTDEL
0
0 - 15
Sequential Start Delay
0 to 150 seconds in 10 second increments
ADVANCE
NO
YES or NO
Advanced Settings
NO: Hide
YES: Show
Table 3. Installer Setup.