3 Make sure all connections are tightened securely and replace the rear access cover. See Figure 7. GROUNDING INSTRUCTIONS- ONLY 3-WIRE CONNECTIONS: A ground strap is installed on this range which connects the center terminal of the neutral terminal block to the range chassis. The ground strap is connected to the range by the center, lowest screw. See Figure 9. The ground strap must not be removed unless National, State or Local Codes do not permit use of a ground strap. Note: If the ground strap is removed for any reason, a separate ground wire must be connected to the separate ground screw attached to the range chassis and to an adequate ground source. 3 & 4-WIRE PERMANENT WIRE CONNECTIONS 3-wire permanent connection - follow steps 1, 2 and 5 below. 4-wire permanent connection - follow all steps below. Before wiring the range, review the suggested power source location drawings in Figure 2. If connecting to a 4-wire electrical system: 1 Follow the manufacturerʼs Installation Instructions supplied with the strain relief clamp and install. 2 Strip insulation away from the ends of the permanent wiring for line 1, line 2 and neutral; also strip ground wire on 4-wire 4-WIRE CONNECTION INSTALLATION MANUAL connections. Tighten all 3 or 4-wire leads to the terminal block. Follow wire locations shown in Figure 10. IMPORTANT DO NOT LOOSEN the factory installed nut connections which secure the range wiring to the terminal block. Electrical failure or loss of electrical connection may occur if these 3 nuts are loosened or removed. Note: For 3-wire permanent connection skip steps 3 and 4 and continue with step 5. 3 Disconnect the ground strap. Remove the factory installed ground screw and plate to release the factory installed copper ground strap from frame of the range. Cut and discard the copper strap from the terminal block. KEEP the ground screw, ground plate and go to step 4. 4 Connect the green ground wire lead to the frame of the range using the ground screw and plate as shown in Figure 11. Be sure to install using the same hole in the frame where the ground screw was originally installed. 5 Make sure all connections are tightened securely and replace the rear access cover. See Figure 7. Note: Non-terminated field wire compression connections must be set at approximately 90 in./lbs. FOR 3 & 4-WIRE PERMANENT CONNECTIONS Connect line 1 here. Cut ground strap. Discard ground strap and ground plate. Connect green insulated copper ground wire with ground screw here. k en Figure 8 3-WIRE CONNECTION Connect line 1 here. Ground strap Note: Install strain relief clamp. Center must always be attached to the center terminal on block. red white gre blac terminal block Connect line 2 here. Note: Install strain relief clamp. Center or white wire must always be attached to the center terminal on block. Connect neutral (white or center) here. A user supplied strain relief clamp must be installed at this location. It requires 1 3/8-inches (3.5 cm) diameter cord kit hole. terminal block line 1 terminal block line 1 line 2 neutral ground strap ground plate ground screw Figure 10 neutral ground strap line 2 ground plate ground screw ground plate ground screw proper ground for 4-wire permanent connection 4-WIRE PERMANENTwCgirreoOulenadNd NECTION ONLY terminal block Connect line 2 here. Connect neutral here. A user supplied strain relief clamp must be installed at this location. It requires 1 3/8-inches (3.5 cm) diameter cord kit hole. ground plate ground screw ground wire lead proper ground for 4-wire permanent connection Figure 9 Figure 11 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

5
INSTALLATION MANUAL
3
Make sure all connections are tightened securely and replace
the rear access cover. See Figure 7.
GROUNDING INSTRUCTIONS- ONLY 3-WIRE CONNECTIONS:
A ground strap is installed on this range which connects the center
terminal of the neutral terminal block to the range chassis. The
ground strap is connected to the range by the center, lowest screw.
See Figure 9.
The ground strap must not be removed unless National,
State or Local Codes do not permit use of a ground strap.
Note:
If the ground strap is removed for any reason, a separate
ground wire must be connected to the separate ground screw
attached to the range chassis and to an adequate ground source.
3 & 4-WIRE PERMANENT WIRE CONNECTIONS
3–wire permanent connection – follow steps 1, 2 and 5 below.
4–wire permanent connection – follow all steps below.
Before wiring the range, review the suggested power source location
drawings in Figure 2. If connecting to a 4-wire electrical system:
1
Follow the manufacturerʼs Installation Instructions supplied
with the strain relief clamp and install.
2
Strip insulation away from the ends of the permanent wiring
for line 1, line 2 and neutral; also strip ground wire on 4-wire
Ground strap
terminal block
Note:
Install strain relief
clamp. Center must
always be attached to the
center terminal on block.
Connect neutral here.
Connect line
1 here.
Connect
line 2
here.
A user supplied strain relief
clamp must be installed at
this location. It requires
1
3
/
8
-inches (3.5 cm)
diameter cord kit hole.
Figure 9
terminal block
w
h
i
t
e
r
e
d
g
r
e
e
n
A user supplied strain
relief clamp must be
installed at this location.
It requires 1
3
/
8
-inches
(3.5 cm) diameter cord
kit hole.
Connect green insulated
copper ground wire with
ground screw here.
Cut ground strap.
Discard ground strap
and ground plate.
Connect neutral (white
or center) here.
Connect line
1 here.
Connect
line 2
here.
b
l
a
c
k
Note:
Install strain relief
clamp. Center or white
wire must always be
attached to the center
terminal on block.
Figure 8
terminal
block
ground
screw
ground plate
ground strap
line 2
neutral
line 1
Figure 10
ground
screw
ground
wire lead
ground
plate
proper ground for
4-wire permanent
connection
Figure 11
4-WIRE PERMANENT CONNECTION ONLY
FOR 3 & 4-WIRE PERMANENT CONNECTIONS
connections. Tighten all 3 or 4-wire leads to the terminal block.
Follow wire locations shown in Figure 10.
IMPORTANT
DO NOT LOOSEN the factory installed nut
connections which secure the range wiring to the terminal
block. Electrical failure or loss of electrical connection may
occur if these 3 nuts are loosened or removed.
Note:
For 3-wire permanent connection skip steps 3 and 4 and
continue with step 5.
3
Disconnect the ground strap. Remove the factory installed
ground screw and plate to release the factory installed copper
ground strap from frame of the range. Cut and discard the
copper strap from the terminal block. KEEP the ground screw,
ground plate and go to step 4.
4
Connect the green ground wire lead to the frame of the range
using the ground screw and plate as shown in Figure 11. Be sure
to install using the same hole in the frame where the ground
screw was originally installed.
5
Make sure all connections are tightened securely and replace
the rear access cover. See Figure 7.
Note:
Non-terminated field wire compression connections must
be set at approximately 90 in./lbs.
4-WIRE CONNECTION
3-WIRE CONNECTION