Tripp Lite SUINT2000XL Owner's Manual for SUINT1000XL/SUINT2000XL/SUINT3000XL - Page 9
Troubleshooting
View all Tripp Lite SUINT2000XL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 9 highlights
200607207 93-2525 230V Smartonline OM.qxd 11/9/2006 3:51 PM Page 9 Troubleshooting The UPS's control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties. Lights (On/Flashing) and Condition On: REPLACE BATT Condition: Replace Battery Solution Let the UPS system charge for at least 12 hours and perform a self test using the "ON/Test Switch" (Basic Operation- UPS Self-Test). If the light continues to stay on, contact Tripp Lite for service. On: BATT LOW, ON BATT Condition: Battery Low Prepare for imminent UPS shutdown. On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports. Condition: On Bypass due to Overload Flashing: OVERLOAD Condition: Short Circuit Remove the cause of the short circuit from the UPS output. On: FAULT, 100% Condition: Battery Voltage too High Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE, 50% Condition: On Bypass due to High Output Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE Flashing: 50% Condition: On Bypass due to Low Bus Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. On: FAULT, BYPASS, LINE, 25% Condition: On Bypass due to Low Output Voltage On: FAULT, BYPASS, LINE Flashing: 25% Condition: On Bypass due to Low Bus Voltage Restart the UPS. If the problem persists, contact Tripp Lite for repairs. Restart the UPS. If the problem persists, contact Tripp Lite for repairs. 9