Bosch NGT745UC Installation Instructions - Page 6
Cutout Dimensions
View all Bosch NGT745UC manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 6 highlights
Countertop Requirements Figure 2 - Cutout Dimensions 6" (152.4mm) Min to Left Side Wall 3" (76.2 mm) Min. to Right Side Wall 1-3/4" (44.5 mm) Min. to Combustible Wall 21" (533.4 mm) cooktop depth 4" (101.6mm) Below Countertop 1/8" (3.5mm) Min Clearance from Cooktop to Start of Radius 2 1/4" (57.2mm) Min. to Counter Front 3" (76.2 mm) Min. to Back Wall 7-3/8"(187.8 mm) Min. to Left Side Wall 4 3/8" (111.6mm) Min. to Right Side Wall Gas Requirements Supply Pressure Propane Gas Installation (NGT Models only) English 4 Table 1: Cutout Dimensions Fig. 2 30" Models A - Cutout B - Cutout C - Corner D - Overall 19-1/8" to 19-7/8" (486.1mm) to (505.6mm) 28-5/8" to 29-3/8" (727.2mm) to (746.6mm) 30" (762mm) 31" (787.4mm) 36" Models 19-1/8 to 19-7/8" (486.1mm) to (505.6mm) 34-5/8" to 35-5/8" (879.6mm) to (899mm) 36" (914.4mm) 37" (939.8mm) • Natural Gas - 6 inches water column (14.9 Millibars) minimum. • Propane Gas -11 inches water column (27.4 Millibars) minimum. NOTE: NGP models cannot be converted for propane use. The propane gas tank must be equipped with its own high pressure regulator in addition to the pressure regulator supplied with this unit. The cooktop is shipped from the factory for use with natural gas. For use with LP, a conversion kit is required and must be purchased separately. Contact BSH or your retailer to obtain kit # NEZ1065. A qualified technician or installer must do the conversion. Leak testing of the appliance shall be conducted according to manufacturerís instructions.