Model 107 Temperature Probe 8. If LoggerNet, PC400, RTDAQ, or PC200W is running on your PC, and the PC to datalogger connection is active, you can click Finish in Short Cut and you will be prompted to send the program just created to the datalogger. 9. If the sensor is connected to the datalogger, as shown in the wiring diagram in step 6, check the output of the sensor in the datalogger support software data display to make sure it is making reasonable measurements. 5. Overview The 107 is a rugged probe that accurately measures air, soil, or water temperature in a variety of applications. The sensor consists of a thermistor encapsulated in an epoxy-filled aluminum housing. This design allows the probe to be buried or submerged in water to 15 m (50 ft) or 21 psi. When measuring air temperature, a 41303-5A radiation shield is normally used to mount the 107 and limit solar radiation loading. See Specifications for a complete list of compatible dataloggers. 6. Specifications Features • Measures air, soil, or water temperature • Compatible with AM16/32-series multiplexers • Easy to install or remove • Durable • Compatible with Campbell Scientific CRBasic dataloggers CR800 series, CR1000, CR3000, and CR5000. Also compatible with Edlog dataloggers CR10(X), CR500, CR510, CR23X, 21X, and CR7(X). Sensor Element: Survival Range: Measurement Range: Measurement Specialties 100K6A1iA thermistor -50 to 100 °C -35 to 50 °C Time Constant in Air: 30 to 60 s in a wind speed of 5 m/s Maximum Cable Length: Accuracy1 Worst case: 1000 ft ±0.4 °C (-24 to 48 °C) ±0.9 °C (-35 to 50 °C) Interchangeability Error: ±0.10 °C (0 to 50 °C) ±0.20 °C at -10 °C ±0.30 °C at -20 °C ±0.40 °C at -30 °C ±0.50 °C at -40 °C CRBasic Therm107() Steinhart-Hart Equation Error: ≤ ±0.01 °C (-35 to 50 °C) 4

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

Model 107 Temperature Probe
8.
If
LoggerNet
,
PC400
,
RTDAQ
, or
PC200W
is running on your PC,
and the PC to datalogger connection is active, you can click
Finish
in
Short Cut
and you will be prompted to send the program just created
to the datalogger.
9.
If the sensor is connected to the datalogger, as shown in the wiring
diagram in step 6, check the output of the sensor in the datalogger
support software data display to make sure it is making reasonable
measurements.
5.
Overview
The 107 is a rugged probe that accurately measures air, soil, or water
temperature in a variety of applications.
The sensor consists of a thermistor
encapsulated in an epoxy-filled aluminum housing.
This design allows the
probe to be buried or submerged in water to 15 m (50 ft) or 21 psi.
When
measuring air temperature, a 41303-5A radiation shield is normally used to
mount the 107 and limit solar radiation loading. See
Specifications
for a
complete list of compatible dataloggers.
6.
Specifications
Features
Measures air, soil, or water temperature
Compatible with AM16/32-series multiplexers
Easy to install or remove
Durable
Compatible with Campbell Scientific CRBasic dataloggers CR800
series, CR1000, CR3000, and CR5000.
Also compatible with Edlog
dataloggers CR10(X), CR500, CR510, CR23X, 21X, and CR7(X).
Sensor Element:
Measurement Specialties 100K6A1iA
thermistor
Survival Range:
–50 to 100 °C
Measurement Range:
–35 to 50 °C
Time Constant in Air:
30 to 60 s in a wind speed of 5 m/s
Maximum Cable Length:
1000 ft
Accuracy
1
Worst case:
±
0.4 °C (–24 to 48 °C)
±
0.9 °C (–35 to 50 °C)
Interchangeability Error:
±
0.10 °C (0 to 50 °C)
±
0.20 °C at –10 °C
±
0.30 °C at –20 °C
±
0.40 °C at –30 °C
±
0.50 °C at –40 °C
CRBasic Therm107()
Steinhart-Hart
Equation Error:
±
0.01 °C (–35 to 50 °C)
4