Campbell Scientific AM16/32B AM16/32B Relay Multiplexer - Page 13

AM16/32B Specifications

Page 13 highlights

AM16/32B Relay Multiplexer FIGURE 2-1. AM16/32B Relay Multiplexer 3. AM16/32B Specifications Power*: Minimum Operating Voltage: Unregulated 12 Vdc from -55° to +40°C = 11.3 Vdc from +40° to +85°C = 11.8 Vdc (See FIGURE 3-1 for relay actuation times vs. temperature and supply voltage.) Current Drain Quiescent: Active: Reset*: Clock*:

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

AM16/32B Relay Multiplexer
FIGURE 2-1.
AM16/32B Relay Multiplexer
3.
AM16/32B Specifications
Power
*
:
Unregulated 12 Vdc
Minimum
Operating Voltage:
from –55° to +40°C = 11.3 Vdc
from +40° to +85°C = 11.8 Vdc
(See FIGURE 3-1 for relay actuation times vs.
temperature and supply voltage.)
Current Drain
Quiescent:
<210 μA
Active:
6 mA typical in “2 x 32” mode
11 mA typical in “4 x 16” mode
Reset
*
:
A continuous signal between 3.3 Vdc and
8 Vdc holds the AM16/32B in an active state
(where a clock pulse can trigger a channel
advance).
A signal voltage <0.9 Vdc
deactivates the AM16/32B (clock pulse will
not trigger a scan advance; AM16/32B is also
reset).
Clock
*
:
On the transition from <1.5 V to >3.3 V, a scan
advance is actuated on the leading edge of the
clock signal; clock pulse should be a minimum
of 1 ms wide; maximum voltage is 8 Vdc.
Operational Temperature
Standard:
–25° to +50°C
Extended:
–55° to +85°C
Operational Humidity:
0 to 95%, non-condensing
3