Campbell Scientific HMP60 HMP60 Temperature and Relative Humidity Probe - Page 17
Campbell Scientific HMP60 Manual
View all Campbell Scientific HMP60 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 17 highlights
HMP60 Temperature and Relative Humidity Probe Black White Blue Brown Clear Temperature Signal Relative Humidity Signal Signal & Power Reference Power Shield FIGURE 7-1. HMP60 wiring TABLE 7-1. Datalogger Connections CR800, CR3000, CR200(X), CR23X, CR1000 Single-Ended Input Single-Ended Input G 12 V Wire Label Temp Signal RH Signal Power & Signal Ground Power 12V Shield Color Black White Blue Brown Clear CR10(X), CR510 Single-Ended Input Single-Ended Input G 12 V G 21X, CR7 Single-Ended Input Single-Ended Input 12 V 7.3 Wiring Connections to Campbell Scientific dataloggers are given in Table 7-1. The probe is measured by two single-ended analog input channels, one for temperature and one for relative humidity. CAUTION Always connect the blue lead to the datalogger first, followed by the black, white, and clear leads. Connect the brown (power) lead last. 7.4 Programming This section is for users who write their own datalogger programs. A datalogger program to measure this sensor can be created using Campbell Scientific's Short Cut Program Builder Software. You do not need to read this section to use Short Cut. 11