Dell PowerEdge MX740c EMC Technical Specifications - Page 15

Standard operating temperature, Expanded operating temperature restrictions

Page 15 highlights

Table 12. Particulate contamination specifications (continued) Particulate contamination Specifications NOTE: This condition applies to data center and nondata center environments. Table 13. Gaseous contamination specifications Gaseous contamination Specifications Copper coupon corrosion rate

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

Table 12. Particulate contamination specifications (continued)
Particulate contamination
Specifications
NOTE:
This condition applies to data center and nondata center
environments.
Table 13. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Standard operating temperature
Table 14. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than 950 m or 3117
ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Humidity percentage range
10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Expanded operating temperature
Table 15. Expanded operating temperature specifications
Expanded operating temperature
Specifications
Continuous Operation
5°C–40°C at 5% to 85% RH with 29°C dew point
NOTE:
Outside the standard operating temperature (10°C–
35°C), the system can operate continuously in temperatures as
low as 5°C and as high as 40°C.
For temperatures 35°C–40°C, derate maximum allowable dry bulb
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
Less than or equal to 1% of annual operating hours
–5°C–45°C at 5% to 90% RH with 29°C dew point
NOTE:
Outside the standard operating temperature (10°C–
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures 40°C–45°C, derate maximum allowable temperature by
1°C per 125 m above 950 m (1°F per 228 ft).
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings maybe reported on the LCD
panel and in the System event log.
Expanded operating temperature restrictions
1.
Do not perform a cold startup below 5°C.
2.
The operating temperature that is specified is for a maximum altitude of 3050 m(10,000 ft).
3.
Low core count processors [Gold 6146,6144,6134,6128,5222,5217,5122] and higher wattage processors [Thermal Design Power
(TDP)>140 W] are not supported.
4.
Non-Dell qualified peripheral cards or peripheral cards greater than 30 W are not supported.
Technical specifications
15