Table 9. Supported video resolution options (continued) Resolution Refresh rate (Hz) 1600 x 1200 60 1680 x 1050 60 1920 x 1080 60 1920 x 1200 60 Color depth (bits) 8, 16, 32 8, 16, 32 8, 16, 32 8, 16, 32 Environmental specifications NOTE: For additional information about environmental certifications, refer to the Product Environmental Datasheet located with the manuals & documents on www.dell.com/support/home. Table 10. Operational climatic range category A2 Temperature Specifications Allowable continuous operations Temperature ranges for altitudes

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11

Table 9. Supported video resolution options (continued)
Resolution
Refresh rate (Hz)
Color depth (bits)
1600 x 1200
60
8, 16, 32
1680 x 1050
60
8, 16, 32
1920 x 1080
60
8, 16, 32
1920 x 1200
60
8, 16, 32
Environmental specifications
NOTE:
For additional information about environmental certifications, refer to the
Product Environmental Datasheet
located
with the manuals & documents on
www.dell.com/support/home
.
Table 10. Operational climatic range category A2
Temperature
Specifications
Allowable continuous operations
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
10–35°C (50–95°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/300 m (33.8°F/984 Ft) above
900 m (2953 Ft)
Table 11. Operational climatic range category A3
Temperature
Specifications
Allowable continuous operations
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
5–40°C (41–104°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Table 12. Operational climatic range category A4
Temperature
Specifications
Allowable continuous operations
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
5–45°C (41–113°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/125 m (33.8°F/410 Ft) above
900 m (2953 Ft)
Table 13. Shared requirements across all categories
Temperature
Specifications
Allowable continuous operations
8