Table 21. Particulate contamination specifications (continued) Particulate contamination Specifications Corrosive dust • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and non-data center environments. Table 22. Gaseous contamination specifications Gaseous contamination Specifications Copper coupon corrosion rate

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17

Table 21. Particulate contamination specifications (continued)
Particulate contamination
Specifications
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than
60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Table 22. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013.
Silver coupon corrosion rate
<200 Å/month as defined by ANSI/ISA71.04-2013.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
PowerEdge R940 technical specifications