Motor Analyzer Motor Measurements Motor Measurements Table 1 is a list of supported motors: Table 1. Motor Configurations Motor type Motor measurement connection Motor winding connection 3-phase asynchronous 3-Wire Direct on Line or 3-Wire connected to VSD WYE or Delta Table 2 is a list of the range and accuracy of the Motor Analyzer-specific functions. See Specifications in the Fluke 430 Series II Users Manual for the specifications of the other functions. Table 2. Motor Analyzer Range and Accuracy Motor Measurement Range Resolution Accuracy Default Limit Mechanical Motor Power 0.7 kW to 746 kW 1 hp to 1000 hp 0.1 kW 0.1 hp ±3 %[1] ±3 %[1] 100 % = nominal power[2] 100 % = nominal power[2] Torque 0 Nm to 25 000 Nm 1 Nm 0 lb ft to 18 500 lb ft 0.1 lb ft ±5 %[1] ±5 %[1] 100 % = nominal torque[2] 100 % = nominal torque[2] rpm Direct on Line VSD Efficiency 000 rpm to 3600 rpm 1 rpm 500 rpm to 4140 rpm 0 % to 100 % 0.1 % ±3 %[1] ±3 %[1] 100 % = nominal rpm[2] NA Unbalance (NEMA MG 1) 0 % to 100 % 0.1 % ±0.15 % 5 % Harmonics Voltage Factor (NEMA MG 1) 0 to 0.20 0.01 ±1.5 % 0.15 Unbalance Derating Factor 0.7 to 1.0 0.1 indicative NA Harmonics Derating Factor 0.7 to 1.0 0.1 indicative NA Total Derating Factor 0.5 to 1.0 0.1 indicative NA [1] Add 5% error when selecting Motor design type Other Specification valid for Motor Power >30 % of rated power, when operating at

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18

Motor Analyzer
Motor Measurements
3
Motor Measurements
Table 1 is a list of supported motors:
Table 2 is a list of the range and accuracy of the Motor Analyzer-specific functions. See
Specifications
in the
Fluke 430 Series II Users Manual
for the specifications of the other functions.
Table 1. Motor Configurations
Motor type
3-phase asynchronous
Motor measurement connection
3-Wire Direct on Line or 3-Wire connected to VSD
Motor winding connection
WYE or Delta
Table 2. Motor Analyzer Range and Accuracy
Motor Measurement
Range
Resolution
Accuracy
Default Limit
Mechanical Motor Power
0.7 kW to 746 kW
0.1 kW
±3 %
[1]
100 % = nominal power
[2]
1 hp to 1000 hp
0.1 hp
±3 %
[1]
100 % = nominal power
[2]
Torque
0 Nm to 25 000 Nm
1 Nm
±5 %
[1]
100 % = nominal torque
[2]
0 lb ft to 18 500 lb ft
0.1 lb ft
±5 %
[1]
100 % = nominal torque
[2]
rpm
1 rpm
±3 %
[1]
100 % = nominal rpm
[2]
Direct on Line
000 rpm to 3600 rpm
VSD
500 rpm to 4140 rpm
Efficiency
0 % to 100 %
0.1 %
±3 %
[1]
NA
Unbalance (NEMA MG 1)
0 % to 100 %
0.1 %
±0.15 %
5 %
Harmonics Voltage Factor
(NEMA MG 1)
0 to 0.20
0.01
±1.5 %
0.15
Unbalance Derating Factor
0.7 to 1.0
0.1
indicative
NA
Harmonics Derating Factor
0.7 to 1.0
0.1
indicative
NA
Total Derating Factor
0.5 to 1.0
0.1
indicative
NA
[1]
Add 5% error when selecting Motor design type Other
Specification valid for Motor Power >30 % of rated power, when operating at <30 % of rated Motor
Power, the mechanical motor power accuracy is ±3 % +0.7 % of rated power and torque accuracy is
±5 % +1.5 % of rated torque.
Specification valid at stable operating temperature. Run the motor for at least 1 hour at full load
(2-3 hours if the motor is 50 HP or higher) to obtain stable temperature.
Motor must be in near steady state mechanical condition.
[2]
For Direct Online Motors the nominal values are identical to the rated values on the Motor Nameplate.
For VSD driven motors the nominal values are based on the actual motor frequency.
Notes:
Rated torque is calculated from rated power and rated speed.
Update rate of Motor Measurements is 1x for each second.
Default Trend duration is 1 week.