Frigidaire FFHP124WS1 Installation Instructions - Page 22
Caution in handling the packed valve integrated in the, outlets of outdoor unit.
View all Frigidaire FFHP124WS1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 22 highlights
5. Pipe length and refrigerant amount for multi split type air conditioner. (see tabel 2.3) Table 2.3 Cooling capacity Connective pipe (BTU/h) length (Lx) Max connective pipe total length (H1) Max height difference (H2) Air purging Additional amount of refrigerant to be charged 26000 25'~66' (x=1, 2, 3) 197' (H1=L1+L2+...+Lx, x≤3) 50' Use vacuum pump. R410a: 0.22ozs/ft (Pipe length-82') 34400 25'~82' (x=1, 2, 3, 4, 5) 246' (H1=L1+L2+...+Lx, x≤5) 50' Use vacuum pump. R410a: 0.22ozs/ft (Pipe length-131') Outdoor unit Lx H1 L1 L2 L3 L4 L5 a b c d e Indoor unit Caution in handling the packed valve integrated in the outlets of outdoor unit. 1. Operation of opening packed valve: Open the valve stem until it hits against the stopper. Do not try to open it further. 2. Operation of closing packed valve: Securely tighten the valve stem with a special tool. Then securely tighten the valve stem cap with a spanner or the like. Refer to the table on page 17 for valve cap tightening torque. Note: There is a charging port integrated in the low side outlet, but not in the high side outlet. The low side outlet is shown in the sketch map below. Refrigerant Outdoor unit A Indoor unit Gas C D B Packed valve Half union Valve body Flare nut Cap Charge port Valve stem Stopper 21 Purging the system