Haier QAS740RMSS Installation Instructions - Page 3

Wire Installation Ground Is Through The, Neutral Wire, Rear Trim Installation, Wire Installation - model

Page 3 highlights

3 REAR TRIM INSTALLATION There are two options for installing the rear trim to the back of the range with the 4 screws provided. The attached spacers must never be removed. Back of Range Rear Trim Spacers Back of Range Rear Trim Spacers Screws Screws 4 3-WIRE INSTALLATION (GROUND IS THROUGH THE NEUTRAL WIRE) Power Cord WARNING Shock Hazard The neutral wire and ground strap must be Terminal block (appearance may vary) connected as shown below for the range to be properly grounded. Do not remove the ground strap. Failure follow this instruction may result in potential Neutral terminal shock hazard. WARNING Fire hazard Terminal block screws must be securely tightened. Ground strap Ground plate Failure to do so may result in potential fire hazard. FOR POWER CORD INSTALLATION A. Remove the 3 lower screws from the terminal Red or Black block. Do not loosen the upper screws. B. Do not cut or remove the ground strap. C. Insert the 3 screws through each power cord Power cord terminal ring and back into the terminal block. Be certain the white wire is in the center. Securely tighten each screw (35 to 50 in-lbs.) FOR CONDUIT INSTALLATION A. Loosen the 3 lower screws on the terminal block. Do not loosen the upper screws. Terminal block B. Do not cut or remove the ground strap. C. Insert the bare wire tip (insulation stripped 5/8") into the bottom terminal block openings. Be certain the white wire is in the center. On certain models, the wire must be inserted through an opening in the ground strap. Securely tighten each screw onto each wire (35 to 50 in-lbs.). Wire tips D. Reinstall terminal block cover. NOTE: For conduit wires using copper wires, the allowable gauge of the individual wires is 6-8 AWG. NOTE: Aluminum building wire may be used but it must Red or Black White be rated for the correct amperage and voltage. For conduit wires using aluminum wires, the allowable gauge of the individual wires is 4-8 AWG. Conduit PROCEED TO STEP 6. Red or Black White Conduit Red or Black 5 4-WIRE INSTALLATION (SEPARATE GROUND WIRE) WARNING The neutral wire of Before-Power Cord and Conduit the supply circuit must be connected to the neutral terminal located in the lower center of the terminal block. The power leads must Terminal be connected to the lower left and the lower block Ground strap right terminals of the terminal block. The grounding lead must be connected to the or frame of the range with the ground plate and the green ground screw. FOR POWER CORD INSTALLATION A. Remove the 3 lower screws from the Ground strap Neutral terminal terminal block. Do not loosen the upper screws. B. Remove the ground screw and ground plate After-Power Cord and retain them. C. Cut the ground strap below the terminal block and discard the lower section. D. Insert the ground screw through the ground plate (removed earlier) and back into the range frame. Tighten securely, but do not over-tighten (15 to 20 in-lbs.) E. Insert the 3 terminal screws through each power cord terminal ring and back into the terminal block. Be certain the white wire is in the center. Securely tighten each screw (35 to 50 in-lbs. F. Reinstall terminal block cover. FOR CONDUIT INSTALLATION Terminal block Red or Black White Ground screw Green or Bare Neutral terminal Ground plate (grounding to range) Red or Black A. Remove the 3 lower screws from the terminal block. Do not loosen the upper screws. After-Conduit B. Remove the ground screw and ground plate and retain them. C. Cut the ground strap below the terminal block and discard the lower section. Terminal block D. Insert the bare ground bare wire tip (insulation stripped 5/8") between the range frame and the ground plate (removed earlier) and secure it in place with the ground screw. Tighten securely, but do not over-tighten (15 to 20 in-lbs). Wire tips Red or Black Ground plate (grounding to range) Red or Black E. Insert the wire tips (insulation stripped 5/8") into the bottom terminal block openings. Be certain the white wire is in the center. On certain models, the wire must be inserted through an opening in the ground strap. Securely tighten each screw onto each wire (35 to 50 in-lbs.) White Ground screw Green or Bare F. Reinstall terminal block cover. NOTE: For conduit wires using copper wires, the allowable gauge of the individual wires is 6-8 AWG. NOTE: Aluminum building wire may be used but it must be rated for the correct amperage and voltage. For conduit wires using aluminum wires, the allowable gauge of the individual wires is 4-8 AWG.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

4
3-WIRE INSTALLATION (GROUND IS THROUGH THE
NEUTRAL WIRE)
WARNING
Shock Hazard
The neutral wire and ground strap must be
connected as shown below for the range to be
properly grounded. Do not remove the ground strap.
Failure follow this instruction may result in potential
shock hazard.
WARNING
Fire hazard
Terminal block screws must be securely tightened.
Failure to do so may result in potential fire hazard.
FOR POWER CORD INSTALLATION
A.
Remove the 3 lower screws from the terminal
block. Do not loosen the upper screws.
B.
Do not cut or remove the ground strap.
C.
Insert the 3 screws through each power cord
terminal ring and back into the terminal block. Be
certain the white wire is in the center. Securely tighten
each screw (35 to 50 in-lbs.)
FOR CONDUIT INSTALLATION
A.
Loosen the 3 lower screws on the terminal block. Do
not loosen the upper screws.
B.
Do not cut or remove the ground strap.
C.
Insert the bare wire tip (insulation stripped 5/8”) into the
bottom terminal block openings. Be certain the white
wire is in the center. On certain models, the wire must be
inserted through an opening in the ground strap. Securely
tighten each screw onto each wire (35 to 50 in-lbs.).
D.
Reinstall terminal block cover.
NOTE:
For conduit wires using copper wires, the
allowable gauge of the individual wires is 6-8 AWG.
NOTE:
Aluminum building wire may be used but it must
be rated for the correct amperage and voltage. For conduit
wires using aluminum wires, the allowable gauge of the
individual wires is 4-8 AWG.
PROCEED TO STEP 6.
3
REAR TRIM INSTALLATION
There are two options for installing the rear trim to the back of the range with the 4 screws
provided. The attached spacers must never be removed.
5
4-WIRE INSTALLATION (SEPARATE GROUND WIRE)
WARNING
The neutral wire of
the supply circuit must be connected to the
neutral terminal located in the lower center
of the terminal block. The power leads must
be connected to the lower left and the lower
right terminals of the terminal block. The
grounding lead must be connected to the
frame of the range with the ground plate and
the green ground screw.
FOR POWER CORD INSTALLATION
A.
Remove the 3 lower screws from the
terminal block.
Do not loosen the upper
screws.
B.
Remove the ground screw and ground plate
and retain them.
C.
Cut the ground strap below the terminal
block and discard the lower section.
D.
Insert the ground screw through the ground
plate (removed earlier) and back into the
range frame.
Tighten securely, but do not
over-tighten (15 to 20 in-lbs.)
E.
Insert the 3 terminal screws through each
power cord terminal ring and back into the
terminal block.
Be certain the white wire is
in the center.
Securely tighten each screw
(35 to 50 in-lbs.
F.
Reinstall terminal block cover.
FOR CONDUIT INSTALLATION
A.
Remove the 3 lower screws from the terminal
block. Do not loosen the upper screws.
B.
Remove the ground screw and ground plate
and retain them.
C.
Cut the ground strap below the terminal block
and discard the lower section.
D.
Insert the bare ground bare wire tip (insulation
stripped 5/8”) between the range frame and the
ground plate (removed earlier) and secure it in
place with the ground screw.
Tighten securely,
but do not over-tighten (15 to 20 in-lbs).
E.
Insert the wire tips (insulation stripped 5/8”) into
the bottom terminal block openings.
Be certain
the white wire is in the center.
On certain
models, the wire must be inserted through an
opening in the ground strap.
Securely tighten
each screw onto each wire (35 to 50 in-lbs.)
F.
Reinstall terminal block cover.
NOTE:
For conduit wires using copper wires, the allowable gauge of the individual wires is 6-8 AWG.
NOTE:
Aluminum building wire may be used but it must be rated for the correct amperage and voltage.
For conduit wires using aluminum wires, the allowable gauge of the individual wires is 4-8 AWG.
Ground
strap
Terminal block
(appearance
may vary)
Neutral
terminal
Power cord
Ground
plate
Power Cord
Red or
Black
Red or
Black
White
Terminal
block
Red or
Black
Red or
Black
Neutral
terminal
Ground plate
(grounding to
range)
Ground
screw
After–Power Cord
Green
or Bare
White
Before–Power Cord and Conduit
Terminal
block
Neutral
terminal
Ground
strap
Ground strap
or
After–Conduit
Terminal
block
Ground plate
(grounding to
range)
Wire
tips
Ground
screw
Red or
Black
Red or
Black
White
Green
or Bare
Wire
tips
Terminal
block
Conduit
Conduit
Red or
Black
Red or
Black
White
Screws
Rear Trim
Back of Range
Screws
Rear Trim
Back of Range
Spacers
Spacers