Hayward Aqua Rite AQ-RT-PRO prior to Oct 08 - Page 18

Wiring, Input Power - t cell 15

Page 18 highlights

Wiring Power must be shut off at the circuit breaker before performing any wiring. Be sure to follow Local and NEC electrical codes. To provide safe operation, the Aqua Rite Pro must be properly grounded and bonded. Input Power: Wire the Aqua Rite Pro to the LOAD SIDE of the filter pump timer. It is very important that the Aqua Rite Pro is powered only when the pump is running. Note that this circuit must be protected by a Ground Fault Circuit Breaker (GFCB). Refer to the wiring label on the Aqua Rite Pro as well as the diagram below to determine correct wiring connections. The Aqua Rite Pro is shipped from the factory with the configuration jumpers in 240VAC position. If using 120VAC, move the jumpers as shown below. IMPORTANT: If a dispensing device will be used (page 17), it must be powered by the same input voltage as the Aqua Rite Pro. For Canadian models, the Aqua Rite Pro shall be connected to a circuit protected by a class A ground fault interrupter. Be sure to connect the ground wire to the green ground screw terminal located on the bottom of the enclosure. 120 VAC AQUA RITE Pro TYPICAL 240 VAC WIRING AQUA RITE Pro TIMECLOCK SUBPANEL PCB PCB BONDING LUG LOAD GND LINE GROUND IMPORTANT: MOVE JUMPERS TO POSITIONS SHOWN BONDING LOOP PUMP Note: Wire the pump directly to the timeclock--do not use the Aqua Rite Pro as a junction box. Bonding: A lug used for bonding is attached to the bottom of the Aqua Rite Pro enclosure (two lugs are provided for Canadian models). The Aqua Rite Pro must be bonded with an 8 AWG copper wire (6 AWG Canada) to the pool bonding system. Refer to the diagram below. Cutout for cell cable Bottom of Aqua Rite Pro Enclosure Second bonding lug for Canadian models only 15 Bonding lug to pool bonding system

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

15
Bonding lug to pool
bonding system
Second bonding lug for
Canadian models only
Cutout for
cell cable
Bottom of
Aqua Rite Pro Enclosure
Wiring
Power must be shut off at the circuit breaker before performing any wiring.
Be sure to
follow Local and NEC electrical codes.
To provide safe operation, the Aqua Rite Pro
must be properly grounded and bonded.
Input Power:
Wire the Aqua Rite Pro to the
LOAD SIDE
of the filter pump timer.
It is very important
that the Aqua Rite Pro is powered
only
when the pump is running.
Note that this circuit
must be protected by a Ground Fault Circuit Breaker (GFCB).
Refer to the wiring label on the Aqua Rite Pro as well as the diagram below to determine
correct wiring connections.
The Aqua Rite Pro is shipped from the factory with the
configuration jumpers in 240VAC position.
If using 120VAC, move the jumpers as
shown below.
IMPORTANT: If a dispensing device will be used (page 17), it must be
powered by the same input voltage as the
Aqua Rite Pro.
For Canadian models, the Aqua Rite Pro shall be connected to a circuit protected by a
class A ground fault interrupter.
Be sure to connect the ground wire to the green ground
screw terminal located on the bottom of the enclosure.
Bonding:
A lug used for bonding is attached to the bottom of the Aqua Rite Pro enclosure (two
lugs are provided for Canadian models).
The Aqua Rite Pro must be bonded with an 8
AWG copper wire (6 AWG Canada) to the pool bonding system.
Refer to the diagram
below.
SUBPANEL
TIMECLOCK
AQUA
RITE Pro
AQUA
RITE Pro
PCB
GND
PCB
BONDING
LUG
BONDING
LOOP
PUMP
LINE
LOAD
GROUND
IMPORTANT:
MOVE JUMPERS
TO POSITIONS SHOWN
TYPICAL 240 VAC WIRING
120 VAC
Note:
Wire the pump directly to the timeclock--do not use the Aqua Rite Pro as a junction box.