Hayward HeatPro Heat Pro Installation - Page 19

General Troubleshooting Guide for Hayward HeatPro Heat Pump

Page 19 highlights

Page 19 of 20 HEATPRO HEAT PUMP HP13023770 Rev: E General Troubleshooting Guide for Hayward HeatPro Heat Pump Problem Possible Cause Possible Solution(s) Unit is not operating. No power to unit Breaker is tripped Thermostat not turned up high enough 5 minute delay timer still running Low water flow Outside temperature too low Fan not functioning Make sure power is on. Check the breaker / see note above Turn thermostat up until unit comes on Be sure the 5 minute delay has passed Make sure filter is clean Make sure filter pump is on Unhook cleaning devices Check outside ambient temperature or wait for warmer temperatures to operate. (refer to Operating section) Call for service. Heat pump is running but is not heating, "Run" light does not come on. Check output air temperature to input air temperature. Differential should be at least 8ºF (4ºC) System Component failure. Low ambient air temperature. Allow outside air temperature to exceed 60ºF, then re-check Call for service. Heat pump runs continually Thermostat set too high Electrical component failure Turn thermostat down Turn off the filter pump. If the unit is still running after 2 minutes, turn off the power to the unit and call for service. Heat pump is cycling (on / off too quickly) Bad valve or improper water flow Low refrigerant, low ambient temp, or high humidity with low ambient temp Check valve settings and ensure water flow is sufficient (is the filter pump running continually?) If heat pump continues to cycle, turn unit off to prevent compressor damage. Check evaporator coil for severe frost. Turn unit off to prevent compressor damage. If heat pump continues to cycle, turn unit off to prevent compressor damage. Water is coming from bottom of unit Condensation Possible water leak This is normal and there is no reason to be concerned Turn the unit off for several hours, but leave the filter pump running continuously. If water quantity decreases, then it is only condensation. Otherwise there is a possible leak. USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Pomona, CA Clemmons, NC Nashville, TN Tel: 908.351.5400 www.haywardpool.com

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21

Page 19 of 20
HEATPRO HEAT PUMP
HP13023770 Rev: E
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Pomona, CA
Clemmons, NC
Nashville, TN
Tel: 908.351.5400
www.haywardpool.com
General Troubleshooting Guide for Hayward HeatPro Heat Pump
Problem
Possible Cause
Possible Solution(s)
No power to unit
Make sure power is on.
Breaker is tripped
Check the breaker / see note above
Thermostat not turned up
high enough
Turn thermostat up until unit comes on
5 minute delay timer still
running
Be sure the 5 minute delay has passed
Make sure filter is clean
Make sure filter pump is on
Low water flow
Unhook cleaning devices
Outside temperature too low
Check outside ambient temperature or wait
for warmer temperatures to operate. (refer to
Operating section)
Unit is not operating.
Fan not functioning
Call for service.
Check output air
temperature to input air
temperature.
Differential
should be at least 8ºF (4ºC)
Low ambient air temperature.
Allow outside
air temperature to exceed 60ºF, then re-check
Heat pump is running but
is not heating, “Run” light
does not come on.
System Component failure.
Call for service.
Thermostat set too high
Turn thermostat down
Heat pump runs
continually
Electrical component failure
Turn off the filter pump. If the unit is still
running after 2 minutes, turn off the power to
the unit and call for service.
Bad valve or improper
water flow
Check valve settings and ensure water flow is
sufficient (is the filter pump running
continually?) If heat pump continues to cycle,
turn unit off to prevent compressor damage.
Low refrigerant, low
ambient temp, or high
humidity with low ambient
temp
Check evaporator coil for severe frost. Turn
unit off to prevent compressor damage.
Heat pump is cycling
(on /
off too quickly)
If heat pump continues to cycle, turn unit off
to prevent compressor damage.
Condensation
This is normal and there is no reason to be
concerned
Water is coming from
bottom of unit
Possible water leak
Turn the unit off for several hours, but leave
the filter pump running continuously.
If
water quantity decreases, then it is only
condensation. Otherwise there is a possible
leak.