Hayward TriStar All TriStar models - Page 7

Start-Up & Operation - variable speed pump

Page 7 highlights

TriStar™ Pump Series Page 7 of 15 Electrical (cont'd.) Wiring WARNING - All electrical wiring MUST be in conformance with all applicable local codes, regulations, and the National Electric Code (NEC). Pump MUST be permanently connected to circuit. If other lights or appliances are also on the same circuit, be sure to add their amp loads before calculating wire and circuit breaker sizes. Use the load circuit breaker as the Master On-Off switch. Full Rate Pumps Motor Specifications Motor Brake Horsepower HP (kW) 0.99 (0.74) 1.39 (1.04) 1.85 (1.38) 2.40 (1.79) 2.70 (2.01) 2.70 (2.01) ** 3.60 (2.69) 3.60 (2.69) * 5.00 (3.73) 1.85 / 0.22 (1.38 / 0.16) 2.40 / 0.28 (1.79 / 0.21) 2.70 / 0.33 (2.01 / 0.25) 0.94 (0.70) 1.25 (0.93) 1.65 (1.23) 2.20 (1.64) 2.60 (1.94) 3.45 (2.57) 1.85 / 0.22 (1.38 / 0.16) 2.40 / 0.28 (1.79 / 0.21) 2.70 / 0.33 (2.01 / 0.25) 0.75 (0.56) 1.00 (0.75) 1.50 (1.12) 2.00 (1.49) 3.00 (2.24) 3.00 (2.24) * Motor Rated Horsepower HP (kW) 0.50 (0.37) 0.75 (0.56) 1.00 (0.75) 1.50 (1.12) 2.00 (1.49) 2.00 (1.49) ** 3.00 (2.24) 3.00 (2.24) * 5.00 (3.73) 1.00 / 0.12 (0.75 / 0.09) 1.50 / 0.18 (1.12 / 0.13) 2.00 / 0.25 (1.49 / 0.19) 0.75 (0.56) 1.00 (0.75) 1.50 (1.12) 2.00 (1.49) 2.50 (1.86) 3.00 (2.24) 1.50 / 0.18 (1.12 / 0.13) 2.00 / 0.25 (1.49 / 0.19) 2.50 / 0.30 (1.86 / 0.22) 0.75 (0.56) 1.00 (0.75) 1.50 (1.12) 2.00 (1.49) 3.00 (2.24) 3.00 (2.24) * Motor Electric V/A Voltage 208 - 230 / 115 208 - 230 / 115 208 - 230 / 115 208 - 230 / 115 208 - 230 208 - 230 ** 208 - 230 208 - 230 / 460 * 208 - 230 208 - 230 208 - 230 208 - 230 230 / 115 230 / 115 230 / 115 230 / 115 230 230 208 - 230 208 - 230 208 - 230 220 / 110 220 / 110 220 / 110 220 220 380 - 415 / 190 * Amps 5.3 - 4.9 / 9.8 7.0 - 6.2 / 12.4 8.5 - 7.4 / 14.8 11.2 - 10.2 / 20.4 11.8 - 11.0 7.0 - 6.6 ** 16.0 - 14.8 9.6 - 9.4 / 4.7 * 21.0 - 19.4 8.6 - 8.2 ¹ 11.4 - 10.4 ² 12.4 - 11.2 ³ 5.4 / 10.8 7.0 / 14.0 7.7 / 15.4 10.8 / 21.6 11.5 13.5 8.6 - 8.2 ¹ 11.4 - 10.4 ² 12.4 - 11.2 ³ 7.0 / 14.0 8.0 / 16.0 9.8 / 19.6 11.0 12.0 4.9 - 4.8 / 9.8 * Wire Size / Breaker AWG 14 14 14 / 12 14 / 10 14 14 ** 12 14 * 10 14 14 14 14 14 / 12 14 / 12 14 / 10 14 12 14 14 14 14 / 12 14 / 12 14 / 10 14 14 14 * Amps 10 / 15 10 / 15 15 / 20 15 / 30 15 10 ** 20 15 / 10 * 30 15 15 15 10 / 15 10 / 20 10 / 20 15 / 30 15 20 15 15 15 10 / 20 10 / 20 15 / 30 15 15 10 / 15 * ¹, ², ³ Low Speed Amps: (¹ 2.8 - 3.0) (² 3.2 - 3.4) (³ 3.8 - 4.1) * Three-Phase (3Φ) Pump - motor starter required ** Three-Phase (3Φ) Pump - variable-speed applications only (Not available as a stand-alone pump. May only be used with SP3220VSC.) Max Rate Pumps 50 Hz Pumps Start-Up & Operation Prior to Start-Up NOTE - If it is necessary to perform a pressure test, prior to initial use to ensure pump is functioning properly, then the following criteria should be maintained for this test: 1. Have a professional perform this test. 2. Ensure all pump and system components are sealed properly to prevent leaks. 3. Remove any trapped air in the system by fully opening filter manual air relief valve until a steady stream of water (not air or air and water mix) is discharged from the valve. 4. Allow no more than 50 psi (345 kPa) at a water temperature no higher than 100° F (38° C). 5. Run pressure test for no longer than 24 hours. Immediately inspect all parts to verify they are intact and functioning properly. WWW.HAYWARDPOOL.COM USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15

TriStar
Pump Series ____________________
____________________________Page 7 of 15
Electrical (cont’d.)
Wiring
WARNING –
All electrical wiring MUST be in conformance with all applicable local codes, regulations,
and the National Electric Code (NEC).
Pump MUST be permanently connected to circuit.
If other lights or appliances are also on the same circuit, be sure
to add their amp loads before calculating wire and circuit breaker sizes.
Use the load circuit breaker as the Master
On-Off switch.
Motor Specifications
Motor Brake Horsepower
Motor Rated Horsepower
Motor Electric V/A
Wire Size / Breaker
HP
(kW)
HP
(kW)
Voltage
Amps
AWG
Amps
0.99
(0.74)
0.50
(0.37)
208 - 230 / 115
5.3 - 4.9 / 9.8
14
10 / 15
1.39
(1.04)
0.75
(0.56)
208 - 230 / 115
7.0 - 6.2 / 12.4
14
10 / 15
1.85
(1.38)
1.00
(0.75)
208 - 230 / 115
8.5 - 7.4 / 14.8
14 / 12
15 / 20
2.40
(1.79)
1.50
(1.12)
208 - 230 / 115
11.2 - 10.2 / 20.4
14 / 10
15 / 30
2.70
(2.01)
2.00
(1.49)
208 - 230
11.8 - 11.0
14
15
2.70
(2.01) **
2.00
(1.49) **
208 - 230 **
7.0 - 6.6 **
14 **
10 **
3.60
(2.69)
3.00
(2.24)
208 - 230
16.0 - 14.8
12
20
3.60
(2.69) *
3.00
(2.24) *
208 - 230 / 460 *
9.6 - 9.4 / 4.7 *
14 *
15 / 10 *
5.00
(3.73)
5.00
(3.73)
208 - 230
21.0 - 19.4
10
30
1.85 / 0.22
(1.38 / 0.16)
1.00 / 0.12
(0.75 / 0.09)
208 - 230
8.6 - 8.2 ¹
14
15
2.40 / 0.28
(1.79 / 0.21)
1.50 / 0.18
(1.12 / 0.13)
208 - 230
11.4 - 10.4 ²
14
15
Full Rate Pumps
2.70 / 0.33
(2.01 / 0.25)
2.00 / 0.25
(1.49 / 0.19)
208 - 230
12.4 - 11.2 ³
14
15
0.94
(0.70)
0.75
(0.56)
230 / 115
5.4 / 10.8
14
10 / 15
1.25
(0.93)
1.00
(0.75)
230 / 115
7.0 / 14.0
14 / 12
10 / 20
1.65
(1.23)
1.50
(1.12)
230 / 115
7.7 / 15.4
14 / 12
10 / 20
2.20
(1.64)
2.00
(1.49)
230 / 115
10.8 / 21.6
14 / 10
15 / 30
2.60
(1.94)
2.50
(1.86)
230
11.5
14
15
3.45
(2.57)
3.00
(2.24)
230
13.5
12
20
1.85 / 0.22
(1.38 / 0.16)
1.50 / 0.18
(1.12 / 0.13)
208 - 230
8.6 - 8.2 ¹
14
15
2.40 / 0.28
(1.79 / 0.21)
2.00 / 0.25
(1.49 / 0.19)
208 - 230
11.4 - 10.4 ²
14
15
Max Rate Pumps
2.70 / 0.33
(2.01 / 0.25)
2.50 / 0.30
(1.86 / 0.22)
208 - 230
12.4 - 11.2 ³
14
15
0.75
(0.56)
0.75
(0.56)
220 / 110
7.0 / 14.0
14 / 12
10 / 20
1.00
(0.75)
1.00
(0.75)
220 / 110
8.0 / 16.0
14 / 12
10 / 20
1.50
(1.12)
1.50
(1.12)
220 / 110
9.8 / 19.6
14 / 10
15 / 30
2.00
(1.49)
2.00
(1.49)
220
11.0
14
15
3.00
(2.24)
3.00
(2.24)
220
12.0
14
15
50 Hz Pumps
3.00
(2.24) *
3.00
(2.24) *
380 - 415 / 190 *
4.9 - 4.8 / 9.8 *
14 *
10 / 15 *
¹
,
²
,
³
Low Speed Amps:
(¹ 2.8 - 3.0) (² 3.2 - 3.4) (³ 3.8 - 4.1)
*
Three-Phase (3
Φ
) Pump - motor starter required
**
Three-Phase (3
Φ
) Pump - variable-speed applications only
(Not available as a stand-alone pump.
May only be used with SP3220VSC.)
Start-Up & Operation
Prior to Start-Up
NOTE
- If it is necessary to perform a pressure test, prior to initial use to ensure pump is functioning properly, then the
following criteria should be maintained for this test:
1.
Have a professional perform this test.
2.
Ensure all pump and system components are sealed properly to prevent leaks.
3.
Remove any trapped air in the system by fully opening filter manual air relief valve until a
steady stream of water (not air or air and water mix) is discharged from the valve.
4.
Allow no more than 50 psi (345 kPa) at a water temperature no higher than 100
°
F (38
°
C).
5.
Run pressure test for no longer than 24 hours.
Immediately inspect all parts to verify they are
intact and functioning properly.
WWW.HAYWARDPOOL.COM
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS