- HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 1
Site Preparation Guide HP 9000 rp4410 and HP 9000 rp4440 Manufacturing Part Number: A9950-96004 Third Edition April 2005 U.S.A. © Copyright 2004-2005 Hewlett-Packard Development Company, L.P. - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 2
to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 3
Contents 1. System Specifications System Configuration 11 Dimensions and Weights 13 Component Dimensions 13 Grounding 14 Electrical Specifications 15 AC Power Cords 15 Circuit Breaker 15 System Power Specifications 16 Power and Cooling 17 Environmental Specifications 19 Temperature and - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 4
Contents Sample Site Inspection Checklist 42 Delivery Survey 45 Information to Collect Before You Contact Support 47 Glossary 49 Index 51 4 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 5
Figures Figure 1-1. HP 9000 rp4410 and HP 9000 rp4440 Server 11 Figure 1-2. Airflow Through HP 9000 rp4410 and HP 9000 rp4440 Server 20 Figure 2-1. Raised Floor Metal Strip Ground System 28 Figure 2-2. Delivery Survey (Part 1 46 Figure 2-3. Delivery Survey (Part 2 47 5 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 6
Figures 6 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 7
technical product and support information for authorized service providers, customer system administrators, and HP support personnel. What's useful information such as restrictions, recommendations, or important details about HP product features. • Commands and options are represented using this - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 8
diagnostics and event monitoring tools, is at the http://docs.hp.com/hpux/diag/ Web site. This site has manuals, tutorials, FAQs, and other reference material. Web Site for HP Technical Support: http://us-support2.external.hp.com HP's IT resource center Web site at http://us-support2.external - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 9
.html • HP-UX Virtual Partitions http://www.hp.com/hpbooks/prentice/ptr_0130352128.html HP Books are available worldwide through bookstores, online booksellers, and office and computer stores. Printing History The Printing History below identifies the edition dates of this manual. Updates are - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 10
10 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 11
Specifications System Configuration Figure 1-1 HP 9000 rp4410 and HP 9000 rp4440 Server The following table describes the component options for the HP 9000 rp4410 and HP 9000 rp4440 servers. Table 1-1 Minimum/Maximum Configuration Component Microprocessors rp4410 rp4440 One or two dual - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 12
Configuration Table 1-1 Minimum/Maximum Configuration (Continued) Component Memory HDDs SCSI LAN PCI Slots Core I/O DVD-ROM External storage Power supply rp4410 rp4440 Supports up to 16 double data rate (DDR) registered ECC memory, in PC2100 DIMMs. An option is available that allows use of - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 13
Dimensions and Weights Dimensions and Weights This section provides dimensions and weights of HP 9000 rp4410 and HP 9000 rp4440 servers. Component Dimensions Table 1-2 Server Component Dimensions Dimension Height-inches (centimeters) Rack configuration Stand-mounted Width-inches (centimeters - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 14
System Specifications Grounding Grounding The site building shall provide a safety ground or protective earth for each AC service entrance to all cabinets. Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the branch-circuit supply - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 15
section provides electrical specifications for your system. AC Power Cords Table 1-3 lists the various power cables available for use with the HP 9000 rp4410 and HP 9000 rp4440 servers. Table 1-3 Power Cords Part Number 8120-5341 8120-1351 8120-1369 8120-1689 8120-2104 8120-6814 8120-0698 8120 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 16
1-4 lists the AC power requirements for the server. The following tables provide information to help determine factor correction Ground leakage current 200 - 240 VAC 180 VAC 264 VAC 50 - 60 Hz Value 1 8 A RMS rp4410: 100A (peak), 55A (average) 0 msec - 1 msec 55A (peak), 33A (average) 1 msec - 2 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 17
1065 1125 Typical a. Maximum power is the sum of the worst case power consumption values of every subsystem in your HP 9000 rp4410 or HP 9000 rp4440 server. These worst case values should be used to calculate the worst case power consumption for your facility installation. b. Typical power - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 18
System Specifications Electrical Specifications Table 1-6 Typical Configuration Power Values (Continued) CPU Qty Memory Gigabytes 4 32 GBa PCI Cards (assuming 10W each) DVDs Hard Disk Drives Core I/O 6 1 2 2 Bulk Power Supplies Typical PowerWatts Typical CoolingBTU/Hr 2 975 3328. - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 19
Specifications Environmental Specifications This section provides the temperature and humidity requirements, noise emission, and air flow specifications for the HP server. Temperature and Humidity The recommended operating range is 20°C to 25°C and 40% - 55% relative humidity. Ambient intake air - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 20
of the PCI cards. CAUTION For maximum cooling effects, ensure that the chassis ventilation holes are not blocked or covered after installation. Figure 1-2 Airflow Through HP 9000 rp4410 and HP 9000 rp4440 Server 20 Chapter 1 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 21
System Specifications Environmental Specifications Acoustic Noise Specification The acoustic noise specification for the HP 9000 rp4410 or HP 9000 rp4440 servers is as follows: • 53 db LpA (sound pressure level at bystander position in a dedicated computer room environment temperature of - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 22
System Specifications Environmental Specifications 22 Chapter 1 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 23
HP 9000 rp4410 or HP 9000 rp4440 server. Electrical Factors NOTE Electrical practices and suggestions in this guide proper installation practices, produces the most trouble-free operation. A detailed discussion of adequate lighting (for equipment servicing) are important safety considerations. - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 24
computer room reduce the possibility of accidents during equipment servicing. Safer servicing is also more efficient and, therefore, less costly Power Quality The HP 9000 rp4410 and HP 9000 rp4440 servers are designed to operate over a wide range of voltages and frequencies. The server is tested and - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 25
: • Fluctuations occurring within the facility's distribution system • Utility service low-voltage conditions (such as sags or brownouts) • Wide phone transmissions Power System Protection You can protect the HP 9000 rp4410 and HP 9000 rp4440 servers from the sources of many of these electrical - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 26
to earth according to IEC 60950). The HP 9000 rp4410 and HP 9000 rp4440 servers require two methods of grounding: • Power distribution system. Power Panel Ground Each power panel should be grounded to the electrical service entrance with green (green and yellow) wire ground conductors. The green - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 27
grounding grid should be connected to the equipment cabinet and electrical service entrance ground at multiple connection points using a minimum #6 AWG the raised floor should be grounded as an absolute safety minimum. HP recommends the following approaches: • Excellent-Add a grounding grid to - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 28
a ground grid with bolted down stringers and corrosion resistive plating (to provide low resistance and attachment points for connection to service entrance ground and HP computer equipment). The use of conductive floor tiles with this style of grid further enhances ground performance. The structure - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 29
installed prior to the arrival of HP equipment. Refer to the appropriate installation guide for installation procedures. Wiring Connections loose or too tight can have a high impedance that causes serious problems, such as erratic equipment operation. A high impedance connection overheats and - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 30
• Acoustics (noise reduction) Computer Room Preparation The following guidelines are recommended when preparing a computer room for installation of an HP 9000 rp4410 or HP 9000 rp4440 server: • Locate the computer room away from the exterior walls of the building to avoid the heat gain from windows - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 31
. An air distribution system should be zoned to deliver an adequate amount of supply air to the cooling air intake vents of the server equipment cabinets. Supply air temperature should be maintained within the following parameters: • Ceiling supply system-From 55°F (12.8°C) to 60°F (15.6°C) • Floor - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 32
near the cooling air intake vents of the HP 9000 rp4410 and HP 9000 rp4440 servers Air Conditioning System Installation All air conditioning equipment voltage potential. ESD can cause component damage during servicing operations. Paper feed problems on high-speed printers are usually encountered in - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 33
formed on the bottom of some raised floor tiles. Although this problem is relatively rare, it may be an issue within your computer room can cause permanent or intermittent failures on your electronic equipment, HP strongly recommends that your site be evaluated for metallic particulate contamination - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 34
General Site Preparation Guidelines Environmental Elements Electrostatic Discharge (ESD) Prevention Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a static charge is determined by the following factors: • Types of materials • Relative - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 35
the installation or operation of an HP 9000 rp4410 or HP 9000 rp4440 server. Facility characteristics are: • Floor loading • Windows • Altitude effects Floor Loading The computer room floor must be able to support the total weight of the installed cabinets, servers, and associated equipment as they - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 36
for the installation of an HP 9000 rp4410 or HP 9000 rp4440 server. Based on specific information provided by HP, Tate Access Floors has approved .0 cm) by 24 in. (61.0 cm) floor panels be used to support the HP installation. NOTE If the specific floor being evaluated or considered is other than - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 37
With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 38
contains information about space requirements for an HP 9000 rp4410 or HP 9000 rp4440 server installation. This data should be used as be eliminated. The locations of lighting fixtures and utility outlets affect servicing operations. Plan equipment layout to take advantage of lighting and utility - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 39
• Equipment cable routing General Site Preparation Guidelines Space Requirements Chapter 2 39 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 40
provided here are intended to ease data calculation for systems that do not conform specifically to the configurations listed in this Site Preparation Guide. Listed below are the conversion factors used in this document, as well as additional conversion factors which may be helpful in determining - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 41
installation schedule • 7 days before installation - Final check made with a HP site preparation specialist to resolve any last minute problems NOTE Not all installations follow a schedule like the one noted above. Sometimes, a server is purchased through another vendor, which can preclude a rigid - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 42
Information Name: Street Address: State or Province: Zip or postal code: Primary customer contact: Secondary customer contact: Traffic coordinator: HP information Sales representative: Representative making survey: Scheduled delivery date: Phone No: City: or Town: Country Phone No.: Phone No - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 43
Power and Lighting No. Area or condition Yes No 13. Are lighting levels adequate for maintenance? 14. Are there AC outlets available for servicing needs? (such as, vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power used? If so, identify type - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 44
Checklist Table 2-5 Site Inspection Checklist (Continued) Please check either Yes or No. If No, include comment# or date 26. Are there any equipment servicing hazards (loose ground wires, poor lighting, and so on)? Cooling No. Area or condition Yes No 27. Can cooling be maintained between 20 - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 45
information in the areas provided on the form (Figure 2-2). Special instructions or recommendations should be entered on the special instructions or recommendations form. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 46
General Site Preparation Guidelines Delivery Survey Figure 2-2 Delivery Survey (Part 1) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb. or kg Depth Height Width Depth Width Height STAIRS Please list number of flights and stairway - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 47
Information to Collect Before You Contact Support Before you contact HP support, you should: Step 1. Check information on troubleshooting and attempt to solve the problem. Refer to "Troubleshooting" in the Operation Guide for your system, available at http://docs.hp.com. • Note failure symptoms and - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 48
Support • Try to determine precisely what did or did not happen Step 2. Collect the following information: • The model number of your server (such as, rp4410 or rp4440) • The product number of your server versions are in use? • When did the problem start? • Have recent changes been made to the system - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 49
excessive heat, or blocking the natural airflow, and connecting wires or cables. The FCC (Federal Communications Commission) regulates a portion of this problem through Part 15 of their rules and regulations. Even more stringent than the FCC Part 15 requirements, Network Equipment Building Standards - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 50
Glossary PCA operational continuity. The documents cover both physical requirements including: Space Planning, Temperature, Humidity, Fire, Earthquake, Vibration, Transportation, Acoustical, Air Quality and Illumination; and electrical criteria including: Electrostatic Discharge (ESD), - HP 9000 rp4410-4 | Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 51
Index A air conditioning system recommendations, 31 air conditioning ducts, 32 air distribution system room space return air, 31 B basic air conditioning equipment requirements, 30 basic air distribution systems, 31 C circuit breaker, 15 computer room safety fire protection, 23 cooling requirements
Site Preparation Guide
HP 9000 rp4410 and HP 9000 rp4440
Manufacturing Part Number: A9950-96004
Third Edition
April 2005
U.S.A.
© Copyright 2004-2005 Hewlett-Packard Development Company, L.P.