HP 9000 rp4410-4 Site Preparation Guide, Third Edition - HP 9000 rp4410/rp4440 - Page 37
Windows
View all HP 9000 rp4410-4 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 37 highlights
General Site Preparation Guidelines Facility Characteristics The following table lists specifications for the Tate Access Floors Series 800 raised floor system. Table 2-3 Typical Raised Floor Specifications Itema Rating Dead load 7 lb/ft2 (34.2 kg/m2) Live load 313 lb/ft2 (1528.3 kg/m2) Concentrated loadb 1250 lb (567 kg) Ultimate load 4,000 lb (1814 kg) per panel Rolling load 400 lb (181 kg) Average floor load 500 lb (227 kg) a. From Table 2-2 on page 36 b. With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Chapter 2 37