HP Integrity Superdome 2 32-socket HP Integrity Superdome 2 User Service Guide - Page 25
Table 11 Computeenclosure PDU power options, Table 12 IOX ac power specifications
View all HP Integrity Superdome 2 32-socket manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Table 11 Compute enclosure PDU power options Source/Circuit type 3-phase 60A Source voltage (nominal) 200-220 VAC line-to-line (phase-to-phase), 3-phase 50Hz/60Hz Power receptacle Plug or connector type required Number of power cords required (per enclosure leaving the rack) IEC 309 60A 3-Pole, IEC 309 60A 3-Pole, 2 4 wire, Blue, 3.6m 4 wire, Blue (11.8ft) power cord 3-phase 32A 220 VAC to 240 VAC IEC 309 32A 4-Pole, IEC 309 32A 4-Pole, 2 line-to-neutral 3-phase 5 wire, Red, 3.6m 5 wire, Red 50Hz/60Hz (11.8ft) power cord Single-phase 63A Single-phase 30A 200V to 240V ac 50Hz/60Hz 200-240 VAC 50Hz/60Hz IEC 309 63A Single IEC 309 63A Single 4 Phase Blue , 3.6m Phase, Blue (11.8ft) power cord NEMA L6-30P Single NEMA L6-30R Single 6 Phase, 3.6m (11.8ft) Phase power cord Table 12 IOX ac power specifications Requirements Nominal input voltage Frequency range (minimum - maximum) Number of phases Rated line current Maximum inrush current Power factor correction Ground leakage current Value 200-240 VAC 50-60 Hz Single-phase 3A 30 A for 20ms 0.97 1 mA Table 13 IOX PDU power options Source/Circuit type Single-phase 30A Source voltage (nominal) 200-240 VAC 50Hz/60Hz Single-phase 32A 200-240 VAC 50Hz/60Hz Power receptacle Plug or connector type required Number of power cords required (per enclosure leaving the rack) NEMA L6-30P Single NEMA L6-30R Single 2 Phase, 3.6m (11.8ft) Phase power cord IEC 309 32A Single IEC 309 32A Single 2 Phase Red, 3.6m Phase, Red (11.8ft) power cord Electrical specifications 25