HP Integrity Superdome SX1000 User Guide, Sixth Edition - HP Integrity Superdo - Page 134
Component Power Requirements, I/O Expansion Cabinet Power Requirements, Table 4-9
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 134 highlights
System Specifications Electrical Specifications Table 4-8 Power Requirements (without Support Management Station) Requirements Value Comments Product Label maximum current, three-phase, five-wire Power factor correction Ground leakage current (mA) 24 (A rms) 0.95 minimum > 3.5 ma Per phase at 200-240VAC See WARNING below. WARNING Beware of shock hazard. When connecting or removing input power wiring, always connect the ground wire first and disconnect it wire last. Component Power Requirements Table 4-8 and Table 4-9 list the AC power requirements for a hp Integrity Superdome and hp 9000 Superdome systems. These tables provide information to help determine the amount of AC power needed for your computer room. Table 4-9 Component Power Requirements (without Support Management Station) Power Required 50Hz or 60 Hza VA Maximum configuration for SD16 8,200 Maximum configuration for SD32 12,196 Cell Board 900 I/O Cardcage 500 a. A number that should be used for planning to allow for enough power to upgrade through the life of the system. I/O Expansion Cabinet Power Requirements The I/O expansion cabinet requires a single phase 200-240VAC input. Table 4-10 lists the AC power requirements for the I/O expansion cabinet. NOTE The IOX accommodates two AC inputs for redundancy 122 Chapter 4