Site Preparation Power Options • To verify the proper wiring for a 4-wire PDCA, use a DVM to measure the voltage at the in-line connector. Voltage should read 200 - 240 Vac phase-to-phase as measured between the connector pins as follows: L1 to L2, L2 to L3, L1 to L3. • To verify the proper wiring for a 5-wire PDCA, use a DVM to measure the voltage at the connector. Voltage should read 200 - 240 Vac phase-to-neutral as measured between the connector pins as follows: L1 to N, L2 to N, L3 to N. Figure 5-8 PDCA Assembly for Options 6 and 7 (4-Wire Unit Shown) Plug (in-line connector not shown) Chapter 5 155
![](/manual_guide/products/hewlettpackard-integrity-superdome-sx1000-user-guide-edition-hp-integrity-superdome-hp9000-superdome-e57a9b4/167.png)
Chapter 5
Site Preparation
Power Options
155
•
To verify the proper wiring for a 4-wire PDCA, use a DVM to measure the voltage at the in-line connector.
Voltage should read 200 - 240 Vac phase-to-phase as measured between the connector pins as follows: L1
to L2, L2 to L3, L1 to L3.
•
To verify the proper wiring for a 5-wire PDCA, use a DVM to measure the voltage at the connector.
Voltage should read 200 - 240 Vac phase-to-neutral as measured between the connector pins as follows: L1
to N, L2 to N, L3 to N.