HP Integrity rx2660 Site Preparation Guide, Third Edition - HP Integrity rx266 - Page 16
Table 1-7 Physical and Environmental Specifications of the Office Friendly Server, Server, Dimensions
View all HP Integrity rx2660 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
Table 1-7 Physical and Environmental Specifications of the Office Friendly Server Condition Typical Heat Release Nominal Airflow 100-127 VAC 200-240 VAC Maximum Airflow @ 35 degrees C1 Weight Server Pedestal Server Dimensions Pedestal Watts Minimum 363 W Config. Maximum 782 W Config. Typical Config. 483 W Watts 363 W 782 W 483 W CFM 45 45 45 m3/hr 76 76 76 CFM 162 162 162 m3/hr 275 275 275 21 kg - 28 30 kg - kg (46 lb - 37 kg 61 lb) (66 lb - 81 lb) D 69 cm W 27.6 cm (with feet) W 12.7 cm (w/o feet) H 50.8 (D 27.2 in W 10.8 in (with feet) W 5.0 in (w/o feet) H 20.0 in) ASHRAE Class 1 Airflow cooling scheme (front to rear) Min Two 4 GB DDR2 DIMMs, no Config PCIe/PCI-X public cards or, RAID card on private I/O slot. Max Eight 4 GB DDR2 DIMMs, three Config PCIe/PCI-X cards on public I/O slots, and RAID card in private slot. Typical Four 4 GB DDR2 DIMMs, one Config PCIe/PCI-X card on public I/O slots, and RAID card in private slot. 1 Derate maximum dry bulb temperature 1 degree / 300 meters above 900 meters. 16 Server Specifications