Electrical configuration NOTE: If configuration of the building electrical system used to power the printer needs to be modified to meet printer requirements, an electrician is required. Make sure that your electrician is appropriately certified according to local regulations and supplied with all the information regarding the electrical configuration. Your printer requires the following electrical components to be supplied and installed by the customer, according to the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed. Single phase power Table 2-4 Single phase line specifications Number of power cords Input voltage Input frequency Maximum load current (per power cord) HP Latex 560/570 Printer Curing 2 ~200-240 V +-10% (two wires and protective earth) 50 / 60 Hz 13 A Power consumption per power cord in printing mode Power consumption in ready mode 2.0 kW 85 W 1.7 kW Circuit breakers NOTE: The circuit breakers must meet the requirements of the printer and shall be in accordance with the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed. The printer requires two power cords that meet the following requirements. Table 2-5 Dedicated lines per SKU Dedicated line Branch circuit breaker Residual current circuit breaker (1) HP Latex 560/570 Printer Curing Not required. Do not overload lines. Refer to Table 2-4 2 poles, 16 A/20 A according to local laws and printer maximum load current Recommended 2 poles, 30 mA residual, at least 20 A capacity (1) Also known as Ground Fault Circuit Interrupter (GFCI) ENWW Electrical configuration 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17

Electrical
configuration
NOTE:
If
configuration
of the building electrical system used to power the printer needs to be
modified
to meet
printer requirements, an electrician is required. Make sure that your electrician is appropriately
certified
according
to local regulations and supplied with all the information regarding the electrical
configuration.
Your printer requires the following electrical components to be supplied and installed by the customer, according
to the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
Single phase power
Table 2-4
Single phase line
specifications
HP Latex 560/570
Printer
Curing
Number of power cords
2
Input voltage
~200-240 V +-10% (two wires and protective earth)
Input frequency
50 / 60 Hz
Maximum load current (per power cord)
13 A
Power consumption per power cord in
printing mode
2.0 kW
1.7 kW
Power consumption in ready mode
85 W
Circuit breakers
NOTE:
The circuit breakers must meet the requirements of the printer and shall be in accordance with the
Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
The printer requires two power cords that meet the following requirements.
Table 2-5
Dedicated lines per SKU
HP Latex 560/570
Printer
Curing
Dedicated line
Not required. Do not overload lines. Refer to Table 2-4
Branch circuit breaker
2 poles, 16 A/20 A according to local laws and printer maximum load current
Residual current circuit breaker (1)
Recommended
2 poles, 30 mA residual, at least 20 A capacity
(1) Also known as Ground Fault Circuit Interrupter (GFCI)
ENWW
Electrical
configuration
7