HP R1500 HP UPS R7000 User Guide - Page 52
Battery specifications, Average battery runtime, Minimum battery runtime
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 52 highlights
Feature Voltage wave shape Surge suppression Noise filtering Specification Sine wave; 5% THD with typical PFC load High-energy 6500 A peak MOVs and line filter for normal and common mode use Battery specifications Feature Type Voltage Charging Specification Each model contains maintenance-free, sealed, valve regulated lead-acid batteries with an 8-year minimum float service life at 25°C (77°F). The battery modules have a battery string voltage of 216 V. Complete charge takes no more than 48 hours. Approximately 3 hours to 80 percent capacity at default nominal utility voltage and no load. Average battery runtime Average battery runtimes are approximate and vary depending on connected equipment, configuration, battery age, temperature, and so on. These estimates are based on the batteries at beginning of life. Load % Estimated battery runtime (minutes) NA/JPN Runtime with one ERM (minutes) Runtime with four ERMs (minutes) INTL NA/JPN INTL NA/JPN INTL 20 52 50 13 80 6 100 4 62 98 15 33 7 18 5 13 117 301 359 37 103 115 21 57 66 15 39 50 Minimum battery runtime Minimum battery runtimes are at beginning of life. Load % Internal battery runtime (minutes) Runtime with one ERM (minutes) Runtime with four ERMs (minutes) NA/JPN INTL NA/JPN INTL NA/JPN INTL 20 42 50 10 80 5 100 3 50 80 95 240 300 12 27 30 80 95 6 16 18 52 60 4 11 13 35 45 Specifications 52