HP Superdome SX2000 Site Preparation Guide, Fourth Edition - HP Integrity Supe - Page 15

Component Power Requirements, Table 1-10 I/O Expansion Cabinet Power Requirements Without SMS

Page 15 highlights

Table 1-8 Power Requirements (Without SMS) (continued) Requirement Product label maximum current, 3-phase, 4-wire Product label maximum current, 3-phase, 5-wire Power factor correction Ground leakage current (mA) Value 44 A rms 24 A rms 0.95 minimum > 3.5 mA Comments Per-phase at 200 to 240 V ac Per-phase at 200 to 240 V ac See the following WARNING. WARNING! Beware of shock hazard. When connecting or removing input power wiring, always connect the ground wire first and disconnect it last. Component Power Requirements Table 1-9 Component Power Requirements (Without SMS) Component Component Power Required 50 Hz to 60 Hz1 Maximum configuration for SD16 8,200 VA Maximum configuration for SD32 12,196 VA Cell board 900 VA I/O card cage 500 VA 1 A number to use for planning, to allow for enough power to upgrade through the life of the system. IOX Cabinet Power Requirements The IOX requires a single-phase 200-240 V ac input. Table 1-10 lists the ac power requirements for the IOX cabinet. NOTE: The IOX accommodates two ac inputs for redundancy. Table 1-10 I/O Expansion Cabinet Power Requirements (Without SMS) Requirement Nominal input voltage Input voltage range (minimum to maximum) Frequency range (minimum to maximum) Number of phases Marked electrical input current Maximum inrush current Power factor correction Value 200/208/220/230/240 V ac rms 170-264 V ac rms 50/60 Hz 1 16 A 60 A (peak) 0.95 minimum Table 1-11 I/O Expansion Cabinet Component Power Requirements Component Fully configured cabinet I/O card cage ICE Component Power Required 50 Hz to 60 Hz 3200 VA 500 VA 600 VA Electrical Specifications 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35

Table 1-8 Power Requirements (Without SMS)
(continued)
Comments
Value
Requirement
Per-phase at 200 to 240 V ac
44 A rms
Product label maximum current, 3-phase, 4-wire
Per-phase at 200 to 240 V ac
24 A rms
Product label maximum current, 3-phase, 5-wire
0.95 minimum
Power factor correction
See the following WARNING.
> 3.5 mA
Ground leakage current (mA)
WARNING!
Beware of shock hazard. When connecting or removing input power wiring, always
connect the ground wire first and disconnect it last.
Component Power Requirements
Table 1-9 Component Power Requirements (Without SMS)
Component Power Required 50 Hz to 60 Hz
1
Component
8,200 VA
Maximum configuration for SD16
12,196 VA
Maximum configuration for SD32
900 VA
Cell board
500 VA
I/O card cage
1
A number to use for planning, to allow for enough power to upgrade through the life of the system.
IOX Cabinet Power Requirements
The IOX requires a single-phase 200-240 V ac input.
Table 1-10
lists the ac power requirements
for the IOX cabinet.
NOTE:
The IOX accommodates two ac inputs for redundancy.
Table 1-10 I/O Expansion Cabinet Power Requirements (Without SMS)
Value
Requirement
200/208/220/230/240 V ac rms
Nominal input voltage
170-264 V ac rms
Input voltage range (minimum to maximum)
50/60 Hz
Frequency range (minimum to maximum)
1
Number of phases
16 A
Marked electrical input current
60 A (peak)
Maximum inrush current
0.95 minimum
Power factor correction
Table 1-11 I/O Expansion Cabinet Component Power Requirements
Component Power Required 50 Hz to 60 Hz
Component
3200 VA
Fully configured cabinet
500 VA
I/O card cage
600 VA
ICE
Electrical Specifications
15