Delivery space requirements, Equipment clearance and floor loading - spare parts
View all HP Xw460c manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
• At least 762 mm (30 in) of clearance is needed in the rear of the rack to provide access to components. • At least 380 mm (15 in) of clearance is needed around a power supply to facilitate servicing. For more information, see "Working space for component access (on page 14)". Delivery space requirements There should be enough clearance to move equipment safely from the receiving area to the computer room. Permanent obstructions, such as pillars or narrow doorways, can cause equipment damage. Delivery plans should include the possible removal of walls or doors. Operational space requirements Other factors must be considered along with the basic equipment dimensions. Reduced airflow around equipment causes overheating, which can lead to equipment failure. Therefore, the location and orientation of air conditioning ducts, as well as airflow direction, are important. Obstructions to equipment intake or exhaust airflow must be eliminated. CAUTION: Do not block venting holes in the covers or side panels. Proper airflow is required to prevent overheating of the unit. The locations of lighting fixtures and utility outlets affect servicing operations. Plan equipment layout to take advantage of lighting and utility outlets. Do not forget to include clearance for opening and closing equipment doors. Clearance at the front and rear of the racks must also be provided for proper cooling airflow through the equipment. If other equipment is located so that it exhausts heated air near the cooling air intakes of the racks, larger space requirements are needed to keep ambient air intake to the racks and equipment within the specified temperature and humidity ranges. Space planning should also include the possible addition of equipment or other changes in space requirements. Equipment layout plans should also include provisions for the following: • Channels or fixtures used for routing data cables and power cables • Access to air conditioning ducts, filters, lighting, and electrical power hardware • Power conditioning equipment • Cabinets for cleaning materials • Maintenance area and spare parts Equipment clearance and floor loading A clearance of 1219 mm (48 in) in front of a configured rack and 762 mm (30 in) to the rear of a configured rack is recommended. All buildings and raised computer room floors are engineered to provide a specific floor loading. Environmental requirements 20