HP rp8400 Site Preparation Guide, Second Edition - HP rp8400 Server Series
HP rp8400 Manual
View all HP rp8400 manuals
Add to My Manuals
Save this manual to your list of manuals |
HP rp8400 manual content summary:
- HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 1
Site Preparation Guide hp rp8400 Server Series Second Edition Manufacturing Part Number: A6093-96014 August 2002 USA - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 2
ii - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 3
Contents 1. System Specifications General 3 Upgrading rp8400 Servers 4 Upgrading the Server 4 Dimensions and Weights 5 Component Dimensions 5 Component Weights 5 Shipping Dimensions and Weights 6 Electrical Specifications 7 Grounding 7 Circuit Breaker 7 System Power Requirements 7 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 4
Contents 4. Pre-installation Survey Pre-installation Survey Content 35 Typical Installation Schedule 36 Site Inspection 37 Delivery Survey 40 A. System Requirements Summary Power Consumption and Air Conditioning 45 Power Consumption and Air Conditioning Requirement 47 Weight 49 B. Conversion - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 5
Tables Table 1-1. Server Component Dimensions 5 Table 1-2. System Component Weights 5 Table 1-3. Shipping Dimensions and Weights 6 Table 1-4. Power Requirements 7 Table 1-5. System Power Requirements 8 Table 1-6. Power Cords 8 Table 1-7. Computer Environment 9 Table 1-8. - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 6
Tables vi - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 7
Floor Metal Strip Ground System 19 Figure 4-1. Delivery Survey (Part 1 41 Figure 4-2. Delivery Survey (Part 2 42 Figure C-1. rp8400 Space Requirements 54 Figure C-2. rp8400 Cabinet Template 57 Figure C-3. Planning Grid 58 Figure C-4. Planning Grid 59 Figure C-5. Planning Grid 60 Figure - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 8
Figures viii - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 9
Preface - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 10
Legal Notices Hewlett-Packard makes no warranty of any kind with regard to this manual, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be held liable for errors contained - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 11
the product label. Safety in Material Handling WARNING Do not lift the server manually. To avoid physical injury you must use a mechanical lifting device. and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 12
caused to radios and TV receivers, etc. Read the instructions for correct handling. EMI Statement (European Union Only) A. NOTE Electrical practices and suggestions in this guide are based on North American practices. For codes and guidelines. Throughout this manual, the [LAHJ] acronym will - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 13
the service guidelines in the hp rp8400 server series EPSS. Lithium Battery Caution CAUTION Danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer's instructions - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 14
Notational Conventions WARNING Warnings highlight procedures or information necessary to avoid injury to personnel. The warning should tell the reader exactly what will result from what actions and how to avoid them. CAUTION A caution highlights procedures or information necessary to avoid - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 15
xv - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 16
xvi - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 17
1 System Specifications This chapter describes the basic rp8400 configuration and its physical specifications and requirements: • "Upgrading rp8400 Servers" on page 4 discusses the additional requirements resulting from upgrading rp8400 Server systems. • "Dimensions and Weights" on page 5 discusses - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 18
System Specifications • "Electrical Specifications" on page 7 discusses the power requirements for the system. • "Environmental Requirements" on page 9 discusses temperature and humidity, power dissipation, and air flow information about the server. 2 Chapter 1 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 19
System Specifications General General This chapter provides the overall specifications of a rp8400 server system. The specifications are listed throughout this chapter in an effort summarizes these specifications to provide a general overview of the requirements of the rp8400 system. Chapter 1 3 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 20
System Specifications Upgrading rp8400 Servers Upgrading rp8400 Servers This section provides the details relating to upgrading a rp8400 Server system. NOTE Ensure that the customer is aware of the iCOD email requirements. Refer to http://docs.hp.com for more details. Upgrading the Server Space - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 21
dimensions for the cabinet and components for a rp8400 server. Table 1-1 Server Component Dimensions Component Width (cm) Depth/ Length installed. See respective Product Support Plan for the PCI card dimensions. Component Weights Table 1-2 lists the server and component weights. To determine - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 22
will vary depending on the PCI card installed. See respective Product Support Plan for the PCI card weight. Shipping Dimensions and Weights Table 1-3 lists the dimensions and weights of the rp8400 server system cabinet with shipping pallet. Table 1-3 Shipping Dimensions and Weights Equipment - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 23
Specifications Electrical Specifications This section provides electrical specifications for rp8400 servers. Grounding The site building shall provide a safety ground/protective earth for each AC service entrance to all rp8400 cabinets. Install a PE (protective earthing) conductor that is - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 24
Table 1-6 lists the various power cables available for use with a rp8400 server. Each power cord is 15 feet (4.5 meters) in length with server cabinet Documentation for installation will accompany the PDU. The documentation may also be found at the external Rack Solutions Web site at http://www.hp - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 25
air intakes rather than check only ambient room conditions. Table 1-7 lists the computer room temperature and humidity specifications for rp8400 servers. Table 1-7 Computer Environment Parameter Temperatureab Operating Range 5ο C to 35ο C (up to 5000 feet) Recommended Operating Range 20ο C to - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 26
Disk Drive 25 Core I/O 29 PCI Power Supply 47 Total maximum configuration rp8400 Server (PA8700) 2986 283.80 430.00 8.60 42.14 17.20 21 case power consumption. Typical power consumption numbers are what HP engineers have measured running power intensive applications. These are generally - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 27
understand the acoustic noise specifications relative to operator positions within the computer room or when adding rp8400 servers to computer rooms with existing noise sources. Air Flow rp8400 servers require that the recommended cabinet air intake temperature be between 68ο F and 77ο F (20ο C and - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 28
System Specifications Environmental Requirements 12 Chapter 1 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 29
This chapter provides guidelines for planning and preparing the site. Careful site planning and preparation ensures trouble-free installation and reliable operation of rp8400 servers. Factors that may contribute to less than optimal equipment operation are also highlighted. • "Electrical Factors" on - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 30
Electrical and Environmental Guidelines • "Environmental Elements" on page 21 discusses computer room preparation, cooling and humidity requirements, dust and pollution control, electrostatic discharge prevention, and acoustics. 14 Chapter 2 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 31
power distribution system for a rp8400 server requires specialized skills. Those coupled with proper installation practices, produces the most trouble-free operation. A detailed discussion of power and adequate lighting (for equipment servicing) are important safety considerations. Federal - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 32
8 summarizes electrical power load (kVa input) requirements for rp8400 servers. These tables provide load requirements for computers, but additional capacity • Fluctuations occurring within the facility's distribution system • Utility service low-voltage conditions (such as sags or brownouts) • Wide - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 33
, testing cannot conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for rp8400 server equipment: • Dedicated power source-Isolates server power distribution system from other circuits in the - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 34
and Environmental Guidelines Electrical Factors Grounding Systems rp8400 servers require two methods of grounding: • Power equipotential ground to all points. Main Building Electrical Ground The main electrical service entrance equipment should have an earth ground connection, as required by - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 35
grid with bolted down stringers and corrosion resistive plating (to provide low resistance and attachment points for connection to service entrance ground and rp8400 server equipment). The use of conductive floor tiles with this style of grid further enhances ground performance. Figure 2-1 Raised - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 36
Hewlett-Packard equipment. Refer to the appropriate installation guide for installation procedures. Wiring Connections Expansion and contraction loose or too tight can have a high impedance that cause serious problems, such as erratic equipment operation. A high impedance connection overheats and - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 37
discharge (ESD) prevention • Acoustics (noise reduction) Computer Room Preparation The following guidelines are recommended when preparing a computer room for a rp8400 server system: • Locate the computer room away from the exterior walls of the building to avoid the heat gain from windows and - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 38
Electrical and Environmental Guidelines Environmental Elements • Humidification • Reheating • Air distribution • System controls adequate to maintain the computer room within the operating ranges listed in Table 1-7 on page 9. Lighting and personnel must also be included. For example, a person - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 39
levels of electrostatic charges. This increases the electrostatic discharge (ESD) voltage potential. ESD can cause component damage during servicing operations. Paper feed problems on high-speed printers are usually encountered in low-humidity environments. Low humidity levels are often the result - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 40
disk drive read/write heads and the disk surface. • Printer-Locate printers and paper products in a separate room to eliminate paper particulate problems. • Eating or drinking-Establish a no-eating or drinking policy. Spilled liquids can cause short circuits in equipment such as keyboards. • Tile - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 41
Electrical and Environmental Guidelines Environmental Elements Although this problem is relatively rare, it may be an issue within your computer room. Since metallic contamination can cause permanent or intermittent failures on your electronic equipment, - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 42
Electrical and Environmental Guidelines Environmental Elements Acoustics Computer equipment and air conditioning blowers cause computer rooms to be noisy. Ambient noise level in a computer room can be reduced as follows: • Dropped ceiling-Cover with a commercial grade of fire-resistant, acoustic - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 43
3 Facility Guidelines This chapter describes facility characteristics and provides guidelines for preparing the computer room. • "Facility Characteristics" on page 28 discusses architectural issues. • "Space Requirements" on page 31 discusses the amount of floor space required by the components. - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 44
installation or operation of a rp8400 server. Facility characteristics are: Refer Floor Loading The computer room floor must be able to support the total weight of the installed computer system as well floor system under consideration for a HP server installation. Raised Floor Loading Raised - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 45
of solid floor or span of raised floor tiles covered by the rp8400 server footprint. Typical Raised Floor Site This section contains an example of cm) by 24 in. (61.0 cm) floor panels be used to support the rp8400 installation. NOTE If the specific floor being evaluated or considered is other than - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 46
With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 47
Requirements This section contains information about space requirements for a rp8400 server. This data should be used as the basic guideline for must be provided for proper cooling airflow through the equipment. The service area space requirements, outlined in Appendix C, are minimum dimensions. If - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 48
templates are provided in Appendix C to show basic equipment dimensions and space requirements for servicing. Be sure to use the appropriate templates for the equipment that is to be installed. The service areas shown on the template drawings are lightly shaded. Removable copies of the equipment - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 49
4 Pre-installation Survey This chapter provides a site survey information packet consisting of an information form and checklists to be used to evaluate a computer facility. The checklists should be completed and the information sheets and information forms filled out by the customer and a Hewlett- - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 50
Pre-installation Survey • "Typical Installation Schedule" on page 36 describes the proposed schedule of installation events. • "Site Inspection" on page 37 provides the on-site inspection checklist. • "Delivery Survey" on page 40 provides the delivery or installation requirement forms. 34 Chapter - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 51
-installation Survey Content The site Pre-installation survey information is designed to identify problems that might occur before, during, or after the installation of the system personnel. • Pre-installation survey information forms-List delivery information and special instructions. Chapter 4 35 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 52
check made with an Hewlett-Packard site preparation specialist to resolve any last minute problems NOTE Not all installations follow a schedule like the one noted above. Sometimes, HP Servers are purchased through another vendor which can preclude a rigid schedule. Other conditions could also - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 53
Pre-installation Survey Site Inspection Site Inspection Table 4-1 contains the basic Customer and Hewlett-Packard information. Table 4-2 contains the Site Inspection Checklist. Table 4-1 Customer and Hewlett-Packard Information Customer Information Name: Street Address: Phone No: City or - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 54
Power and lighting No. Area or condition Yes No 13. Are lighting levels adequate for maintenance? 14. Are there AC outlets available for servicing needs? (i.e. vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power used? If so, identify type - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 55
purposes? 24. Is there a fire protection system in the computer room? 25. Is antistatic flooring installed? 26. Are there any equipment servicing hazards (loose ground wires, poor lighting, etc.)? Cooling No. Area or condition Yes No 27. Can cooling be maintained between 20 °C and - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 56
the appropriate information in the areas provided on the form. Special instructions or recommendations should be entered on the special instructions or recommendations form. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 57
Pre-installation Survey Delivery Survey • Special security requirements applicable to the facility, such as security clearance Figure 4-1 Delivery Survey (Part 1) DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes No Circle the location of the dock and give street - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 58
Pre-installation Survey Delivery Survey Figure 4-2 Delivery Survey (Part 2) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb or kg) Depth Height Width Depth Height Width STAIRS Please list number of flights and stairway dimensions. Number - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 59
A System Requirements Summary This appendix summarizes the requirements that must be considered in preparing the site for a rp8400 server. • "Power Consumption and Air Conditioning" on page 45 provides tables to determine the overall power consumed and the air conditioning required for a specific - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 60
System Requirements Summary • "Power Consumption and Air Conditioning Requirement" on page 47 provides tables to determine the overall power required for a specific system configuration. • "Weight" on page 49 provides tables to determine the overall weight of a specific system configuration. 44 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 61
initial installation or as a later update. Refer to the applicable documentation for such devices to determine the power and air-conditioning that is required to support these devices. Appendix A 45 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 62
System Requirements Summary Power Consumption and Air Conditioning Table A-1 Example Power Consumption (Theoretical Maximum) and Air Conditioning Requirement Summary Component Quantity Chassis 1 Cell Board (PA8700) 4 PCI Card (Maximum 25W) 16 Power Supply (BPS) 6 DVD 2 Disk Drive 4 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 63
System Requirements Summary Power Consumption and Air Conditioning Requirement Power Consumption and Air Conditioning Requirement Table A-3 Example Power Consumption (Typical) and Air Conditioning Requirement Summary Component Chassis Cell Board (PA8700) PCI Card (25W max) Power Supply (BPS) DVD - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 64
consumption of every subsystem in the box, and should be used to size worst case power consumption. Typical power consumption numbers are what HP engineers have measured running power intensive applications. These are generally lower than maximum power numbers due to the fact that getting all of - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 65
System Requirements Summary Weight Weight To determine overall weight, follow the examples in Table A-5, then complete the entries in Table A-6. Table A-5 Example Weight Summary Component Cell Boards Quantity 4 PCI Card (varies - 4 used A3739B here) Power Supply (BPS) 6 DVD 2 Disk Drive - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 66
System Requirements Summary Weight 50 Appendix A - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 67
in this appendix are intended to ease data calculation for systems that do not conform specifically to the configurations listed in this Site Preparation Guide. Listed below are the conversion factors used in this document, as well as additional conversion factors which may be helpful in determining - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 68
Conversion Factors • Refrigeration - 1 watt = .86 kcal/h - 1 watt = 3.413 Btu/h - 1 watt = 2.843-4 tons - 1 ton = 200 Btu/min - 1 ton = 12,000 Btu/h - 1 ton = 3,517.2 W • Metric equivalents - 1 centimeter = 0.3937 in - 1 meter = 3.28 ft - 1 meter = 1.09 yds - 1 in. = 2.54 cm - 1 ft = 0.305 m - 1 CFM - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 69
C Templates This appendix contains blank floor plan grids and equipment templates. Combine the necessary number of floor plan grid sheets to create a scaled version of the computer room floor plan. Appendix C 53 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 70
Templates Figure C-1 on page 54 illustrates the overall dimensions required for a rp8400 system. Figure C-1 rp8400 Space Requirements 54 Appendix C - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 71
same scale as the floor plan grid (1/4 inch = 1 foot). These templates are provided to show basic equipment dimensions and space requirements for servicing. The service areas shown on the template drawings are lightly shaded. The equipment templates should be used with the floor plan grid to define - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 72
Templates Computer Room Layout Plan Computer Room Layout Plan Use the following procedure to create a computer room layout plan: Step 1. Remove several copies of the floor plan grid. Step 2. Cut and join them together (as necessary) to create a scale model floor plan of your computer room. Step 3. - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 73
plan to the site survey (Table 4-1 and Table 4-2) located in Chapter 4, "Preinstallation Survey." Hewlett-Packard installation specialist use this floor plan during equipment installation. Figure C-2 rp8400 Cabinet Template Appendix C 57 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 74
Templates Computer Room Layout Plan Figure C-3 Planning Grid Scale: 1/4 inch = 1 foot 60SP016A 12/20/99 58 Appendix C - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 75
Figure C-4 Planning Grid Scale: 1/4 inch = 1 foot Templates Computer Room Layout Plan Appendix C 60SP016A 12/20/99 59 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 76
Templates Computer Room Layout Plan Figure C-5 Planning Grid Scale: 1/4 inch = 1 foot 60SP016A 12/20/99 60 Appendix C - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 77
Figure C-6 Planning Grid Scale: 1/4 inch = 1 foot Templates Computer Room Layout Plan Appendix C 60SP016A 12/20/99 61 - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 78
Templates Computer Room Layout Plan Figure C-7 Planning Grid Scale: 1/4 inch = 1 foot 60SP016A 12/20/99 62 Appendix C - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 79
Index A air conditioning system recommendations, 22 air conditioning ducts, 23 air distribution system room space return air, 23 air ducts, 11 illustrated, 11 average floor loading, 29 B basic air conditioning equipment requirements, 21 basic air distribution systems, 22 C circuit board dimensions - HP rp8400 | Site Preparation Guide, Second Edition - HP rp8400 Server Series - Page 80
Index power system protection, 16 preinstallation survey, 33 R raised floor ground system, illustrated, 19 grounding, 19 restricted rights notices, x S shipping dimensions and weights, 6 site inspection, 37 sources of electrical disturbances, 16 space requirements, 31 computer room layout, 56