Honeywell 5890PI Installation Instructions - Page 1
Honeywell 5890PI Manual
View all Honeywell 5890PI manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 1 highlights
N5987-1 3/98 ® For use with Q.E.D. control panels only. Previous Menu No. 5890PI PASSIVE INFRARED MOTION DETECTOR/TRANSMITTER INSTALLATION INSTRUCTIONS GENERAL INFORMATION The 5890PI Passive Infrared Motion Detector/Transmitter is a battery-operated wireless device intended for use as part of a 5800 series wireless alarm system. Designed for use in commercial and residential installations, the 5890PI is a wall mounted unit with a standard lens that provides wide-angle protection up to a range of 35 ft (10.6m). For best coverage, mount the detector so that the likely direction of intruder motion is across the pattern. When installed per the guidelines, the Split Zone Optics technology in the 5890PI provides reasonable false alarm protection against pets and other animals up to 40 lbs. This document provides installation instructions for the 5890PI, but the installer must be familiar with the installation instructions for the 5800 Wireless Alarm System with which the 5890PI is intended to be used. FEATURES • Split-Zone Optics provides pet immunity against animals up to 40 lbs. • Wireless operation for fast installation. • Dual-element pyro-electric sensor provides positive protection while minimizing false alarms. • Alternate polarity pulse count option offers greater stability in adverse environments. • Provision to turn LED on while WalkTesting (LED is turned off after testing). • Tamper-protected cover - unit transmits message if cover is removed. • Wall or corner mounting options. SYSTEM DESCRIPTION Optical System: Uses efficiently designed Fresnel lenses with Split-Zone Optics. Radio Transmitter: The built-in transmitter serves only as the communication link to the alarm system's Receiver/Control, and can send alarm, tamper, supervisory, and battery status messages to the system's receiver/control. The transmitter is not used for detection purposes. Each detector has a unique ID code permanently assigned at the factory. You must enroll this ID into the control system at the time of installation. This allows each detector used in the system to be uniquely identified. You must program the control to enroll the 5890PI as an "RF" type unit (i.e., supervised RF). To conserve battery life during normal operation, no more than one transmission sequence will occur within a 3-minute period. There is no such time restriction in "Test" mode. Alternate Polarity Pulse Count: Two jumper-selectable detection response modes are provided: Instant response (Pulse Count OFF) and Alternate Polarity Pulse Count (Pulse Count ON). With Pulse Count OFF, any detected change in infrared energy will trigger an immediate alarm signal. This mode is recommended when the detector is used to monitor a narrow hallway where coverage is provided by only a single zone. Use the Pulse Count ON mode when the detector is installed in areas where periodic changes in infrared energy levels are normal (for example, where forced-air heating ducts are present). In this mode, at least two changes in infrared energy must be detected within a short period before an alarm will be triggered. Important Note: For pet immune applications, Pulse Count ON is recommended. SPECIFICATIONS Pet Immune Lens : 35 ft x 45 ft (10.6m x 13.7m). 30 zones (8 long, 7 over 7 intermediate, 4 over 4 short range). Pulse Count: Installer-selectable On/Off link. Detectable Walk Rate: 0.5 - 10 ft/sec (0.15 - 1.5m/sec). Mtg. Height: Walk Test Indicator: Batteries: 0perating Temperature: 7.0 ft recommended (2.1m), but may be mounted at other heights (see Table 1). Red LED with Test/Normal (disable) link. Two 3-volt Lithium batteries. Use only Ademco No. 466, Duracell DL123A, Panasonic CR123A, Sanyo CR123A or Varta CR123A. 32°F - 122°F (0°C - 50°C). Operating Humidity: Up to 95% RH (max.), non- condensing. Dimensions: 2-11/16"W x 5"H x 1-7/8"D 68mm x 127mm x 48mm. 25' (7.6m) 0 25' (7.6m) 7.5' (2.3m) 10' (3m) 20' (6m) ALTERNATE COUNT POLARITY EACH ZONE CONSISTS OF 2 FIELDS 30' 35' (9m) (10.6m) BATTERY INSTALLATION 1. Remove front cover by inserting a large screwdriver blade (or small coin) in groove between cover and base at the location shown in Figure 2; rotate blade to override snap fit, then lift cover off. 2. Observing correct polarity, install the two Lithium batteries (supplied) into the battery holders, as shown in Figure 5. Make sure the batteries are firmly seated. 3. Replace the cover (snap fit). Battery Caution: Risk of fire, explosion, and burns. Do not recharge, disassemble, heat above 100°C, or incinerate. Dispose of used batteries promptly. Keep away from children. Programming Note: If you have not programmed the detector's ID into the system (i.e., this is an initial detector installation), refer to the PROGRAMMING section below and perform the ID enrolling procedure before mounting or testing the detector. PROGRAMMING You must enroll the detector's ID during installation of the system. You should program the 5890PI as an "RF" type unit (i.e., supervised RF). and the "Loop" number as "1". To program the detector, place the LED jumper in the TEST position (see Figure 5), the Pulse Count jumper in the OFF position, batteries installed and cover on. Temporarily cover the lens (a cloth will do) to prevent any activation by the detector. With the control in Zone Programming mode, at the "Input serial number" prompt, remove the cloth cover and motion your hand over the lens to activate the detector and cause it to send a FAULT; then cover the lens again to send a RESTORE. Repeat this procedure to confirm the serial number enrolled. Alternatively, you can enter the serial number manually. Return LED jumper to the NORMAL position. See the control unit's installation instructions for further details. INSTALLATION HINTS • Do not install where the detector is exposed to direct sunlight or directly above strong sources of heat. • Make sure the detection area does not have obstructions (curtains, screens, large pieces of furniture, plants, etc.) which may block the pattern of coverage. • Avoid locating a unit in areas which contain objects likely to produce a rapid change in temperature, such as central heating, radiators, or ducts (or heaters of any kind), air conditioners, open flame, etc. • Do not mount on an unstable surface. 0 0 10' 20' 30' 35' (3m) (6m) (9m) (10.6m) Figure 1. Protection Pattern 1