Troubleshooting (continued) Problem Timer is losing time (continued). Check Action - high limit control. If clock powered through system transformer, power to clock and equipment may be Off on safety. Wire separate transformer to power clock. Timer does not run. - filter. May be clogged. Safety limit on equipment may cut off power to system. - voltage across the C and R terminals. Replace filter and reset clock. Remove the thermostat from the wallplate or subbase, and measure the voltage. Refer to page 19 for cause and action. (continued) 18 69-0563-2

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

18
69-0563—2
Troubleshooting (continued)
(continued)
Problem
Check
Action
Timer is losing time
(continued).
high limit control. If clock
powered through system trans-
former, power to clock and
equipment may be Off on
safety.
Wire separate transformer to power clock.
filter. May be clogged. Safety
limit on equipment may cut off
power to system.
Replace filter and reset clock.
Timer does not run.
voltage across the C and R
terminals.
Remove the thermostat from the wallplate or
subbase, and measure the voltage. Refer to
page 19 for cause and action.