LG DH65EL Service Manual - Page 18

Replace, Refrigeration, System

Page 18 highlights

3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM 1. When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes. 3. Solder service valves into the pinch-off tube ports, leaving the valves open. 4. Solder the pinch-off tubes with service valves. 5. After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures. 6. Evacuate as follows. 1) Connect the vacuum pump, as illustrated in Figure 31A. 2) Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system. CAUTION If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump. 3) Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump. 4) Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C. Discharge the line at the manifold connection. 5) The system is now ready for final charging. 7. Recharge as follows : 1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened. 2) Connect the charging cylinder as shown in Figure 31B. With valve C open, discharge the hose at the manifold connection. 3) Open valve A and allow the proper charge to enter the system. Valve B is still closed. 4) If more charge is required, the high-side will not take it. Close valve A. 5) With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the Low- side. b. Watch the Low-side gauge; allow pressure to rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the charge is in the system. 6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection. NOTE: REFRIGERANT R134a IS USED IN SOME MODELS. CHECK THE SPECIFICATION LABEL ON THE CABINET. When discharging refrigerant R134a, purging instrument should be used only for R134a, without mixing that of refrigerant R22. When checking the leakage of refrigerant R134a, leakage test tool should be used only for R134a. The pump for discharging should be high efficiency. Final discharging value must be managed below 0.5 Torr. Maximum water should be less than 150mg in the cycleall tubes and H/E assembly-system. If water quantity is over 150mg, it causes acid or corrosion in the cycle system and the capillary tube to be clogged by water and harmful materials. Models charged with refrigerant R134a should be used dryer to prevent water from overflowing. -18-

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

3.4
HOW
TO
REPLACE
THE
REFRIGERATION
SYSTEM
1.
When
replacing
a
refrigeration
component,
be
sure
to
discharge
the
refrigerant
system
by
using
a
refrigerant
recovery
system.
2.
After
discharging
the
unit
completely,
remove
the
desired
component,
and
unbraze
the
pinch
-off
tubes.
3.
Solder
service
valves
into
the
pinch
-off
tube
ports,
leaving
the
valves
open.
4.
Solder
the
pinch
-off
tubes
with
service
valves.
5.
After
doing
the
above
procedures,
the
valve
must
be
closed
and
left
in
place
on
the
system
for
any
subsequent
procedures.
6.
Evacuate
as
follows.
1)
Connect
the
vacuum pump,
as
illustrated
in
Figure
31A.
2)
Start
the
vacuum
pump,
slowly
open
manifold
valves
A
and
B
two
full
turns
counterclockwise
and
leave
the
valves
open.
The
vacuum
pump
is
now
pulling
through
valves
A
and
B
to
valve
C
by
means
of
the
manifold
and
entire
system.
CAUTION
If
high
vacuum
equipment
is
used,
just
crack
valves
A
and
B
for
a
few
minutes,
then
open
slowly
with
the
two
full
turns
counterclockwise.
This
will
keep
oil
from
foaming
and
being
drawn
into
the
vacuum
pump.
3)
Operate
the
vacuum
pump
for
20
to
30
minutes,
until
600
microns
of
vacuum
are
obtained.
Close
valves
A
and
B,
and
observe
vacuum
gauge
for
a
few
minutes.
A
rise
in
pressure
would
indicate
a
possible
leak
or
moisture
remaining
in
the
system.
With
valves
A
and
B
closed,
stop
the
vacuum
pump.
4)
Remove
the
hose
from
the
vacuum
pump
and
place
it
on
the
charging
cylinder.
See
Figure
31B.
Open
valve
C.
Discharge
the
line
at
the
manifold
connection.
5)
The
system
is
now
ready
for
final
charging.
7.
Recharge
as
follows
:
1)
Refrigeration
cycle
systems
are
charged
from
the
High
-side.
If
the
total
charge
cannot
be
put
in
the
High
-side,
the
balance
will
be
put
in
the
suction
line
through
the
access
valve
which
you
installed
as
the
system
was
opened.
2)
Connect
the
charging
cylinder
as
shown
in
Figure
31B.
With
valve
C
open,
discharge
the
hose
at
the
manifold
connection.
3)
Open
valve
A
and
allow
the
proper
charge
to
enter
the
system.
Valve
B
is
still
closed.
4)
If
more
charge
is
required,
the
high
-side
will
not
take
it.
Close
valve
A.
5)
With
the
unit
running,
open
valve
B
and
add
the
balance
of
the
charge.
a.
Do
not
add
the
liquid
refrigerant
to
the
Low
-
side.
b.
Watch
the
Low
-side
gauge;
allow
pressure
to
rise
to
30
lbs.
c.
Turn
off
valve
B
and
allow
pressure
to
drop.
d.
Repeat
steps
B
and
C
until
the
balance
of
the
charge
is
in
the
system.
6)
When
satisfied
the
unit
is
operating
correctly,
use
the
pinch
-off
tool
with
the
unit
still
running
and
clamp
on
to
the
pinch
-off
tube.
Using
a
tube
cutter,
cut
the
pinch
-off
tube
about
2
inches
from
the
pinch
-off
tool.
Use
sil-fos
solder
and
solder
pinch
-off
tube
closed.
Turn
off
the
unit,
allow
it
to
set
for
a
while,
and
then
test
the
leakage
of
the
pinch
-off
connection.
NOTE:
REFRIGERANT
R134a
IS
USED
IN
SOME
MODELS.
CHECK
THE
SPECIFICATION
LABEL
ON
THE
CABINET.
When
discharging
refrigerant
R134a,
purging
instrument
should
be
used
only
for
R134a,
without
mixing
that
of
refrigerant
R22.
When
checking
the
leakage
of
refrigerant
R134a,
leakage
test
tool
should
be
used
only
for
R134a.
The
pump
for
discharging
should
be
high
efficiency.
Final
discharging
value
must
be
managed
below
0.5
Torr.
Maximum
water
should
be
less
than
150mg
in
the
cycle
-
all
tubes
and
H/E
assembly
-system.
If
water
quantity
is
over
150mg,
it
causes
acid
or
corrosion
in
the
cycle
system
and
the
capillary
tube
to
be
clogged
by
water
and
harmful
materials.
Models
charged
with
refrigerant
R134a
should
be
used
dryer
to
prevent
water
from
overflowing.
—18-