LG HBLG2350E Service Manual - Page 18

Troubleshooting Guide

Page 18 highlights

4.3 TROUBLESHOOTING GUIDE In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but poor cooling Ineffective Cooling Check of cold air circulation for smooth flow. Dirty indoor coil (Heat exchanger) Malfunction of fan Clogged of air filter Obstruction at air outlet Stop of auto air-swing Check of outdoor coil (heat exchanger) & the fan operation. Check gas leakage. Repair gas leak. Replacement of unit if the unit is beyond repair. Correct above trouble Check clogging in refrigeration circuit. Repair clogging in refrigeration circuit. Satisfactory operation with temperature difference of inlet & outlet air ; 44.6~50°F Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes - 18 - Check heat load increase. Unexpected residue Overloaded Circuit Check of inside gas pressure. Adjusting of refrigerant charge Malfunction of compressor Replacement of compressor LGE Internal Use Only

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31

- 18 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling
Ineffective Cooling
Check of outdoor coil
(heat exchanger) & the fan
operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ; 44.6~50
°
F
Check heat load increase.
Unexpected residue
Overloaded Circuit
Check of inside gas
pressure.
Adjusting of refrigerant
charge
Malfunction of compressor
Replacement of
compressor
Check of cold
air circulation
for smooth flow.
Dirty indoor coil
(Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Correct above trouble
Stop of auto air-swing
Check clogging in
refrigeration circuit.
Repair clogging in
refrigeration circuit.