LiftMaster LM21XP LM21XP Manual - Page 7

Connections Of Initiating Devices And, Accessories - door openers

Page 7 highlights

WIRING CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay. NOTE: For low voltage wiring #18 AWG is recommended. Normally Open "2-Wire," Class B Style A Initiating Devices Connect wiring from N/O initiating device loop to positions 3 and 4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained within the accessory pack. (Figure 3). Observe proper polarity, 3 (+), 4 (-) when attaching to the release device's terminal board. NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit. OR Normally Open "4-Wire," Class B Style A Initiating Devices Connect wiring from N/O 4-Wire initiating device loop to positions 3 and 4, making sure an end-of-line supervisory resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4 or 5, depending upon the type of smoke detector being used. Observe proper polarity, 3 (+), 4 (-) when attaching to the release device's terminal board. NOTE: Make certain that the factoryinstalled jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit. OR Normally Closed "4-Wire," Class B Style A Initiating Devices After removing the factory-installed jumper between terminal positions 5 and 6, connect wiring from N/C 4-Wire initiating device loop to positions 5 and 6 (Figure 6). This option is a supervised, current-limited circuit. NOTE: Make certain that the factory-installed resistor between positions 3 and 4 remains in place. NOTE: End-of-line devices must be installed adjacent and after the last initiating device. Initiating device loops are supervised and cannot be direct series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signaling for simultaneous closure on multiple doors, call technical support, 1-888-528-7870. Incorrect wiring between devices may cause damage to the release control circuit and void warranty. OR Relay Module Installation as described on the following page. WARNING To prevent possible SERIOUS INJURY or DEATH: CAUTION • End-of-line devices MUST be installed for supervision of electrical power to 4-wire smoke detector. • DO NOT install this device on a motorized door without an electric safety edge. FIGURE 3 10k Ohm @1/2 watt Supervisory Resistor (LMEOLRES-10) - IN/OUT + OUT + IN - IN/OUT + OUT + IN 24Vdc Power from Terminal Strip 3 NOTE: Follow this method of attachment when using LM2W-B, 4 LM2WT-B, or other 2-wire 24Vdc smoke detectors. FIGURE 4 NOTE: Follow this method of attachment when using (-) LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors. Power from Control Panel (+) Terminal Strip 3 LMEOLR1224 12/24 Vdc EOL Relay 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) COM NO - IN/OUT + OUT + IN COM NO - IN/OUT + OUT + IN 4 FIGURE 5 NOTE: Follow this method of attachment when using (+) LM1424, LM1412, or other N/O 4-wire smoke detectors. Power from Control Panel (-) (+) Alarm Contacts (-) Style A (N/O) (+) (-) LMEOLR1224 12/24 Vdc EOL Relay Terminal Strip (+) 3 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) 4 (-) FIGURE 6 IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support. (-) Power from Control Panel (+) NOTE: Generic version of a N/C 4-wire smoke detector is shown. (+) (-) (+) (-) N/C C N/C C LMEOLR1224 12/24 Vdc EOL Relay Terminal Strip Purple 5 6 7 IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

7
CONNECTIONS OF INITIATING DEVICES AND
ACCESSORIES
A maximum of 4 smoke detectors may be installed with this
device. Refer to NFPA 72 and NFPA 80 for instructions
concerning proper placement and detection coverage. End-of-line
devices must be installed for supervision of electrical power to
4-wire smoke detector. When using 4-wire smoke detectors with
this device, electrical supervision must be provided by means of a
UL/ULC listed end-of-line relay.
NOTE:
For low voltage wiring #18 AWG is recommended.
Normally Open “2-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O initiating device loop to positions 3 and
4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained
within the accessory pack. (Figure 3). Observe proper polarity, 3
(+), 4 (–) when attaching to the release device’s terminal board.
NOTE:
Make certain that the factory-installed jumper between
terminal positions 5 and 6 remains in place.
This option is a
supervised, current-limited circuit.
OR
Normally Open “4-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O 4-Wire initiating device loop to
positions 3 and 4, making sure an end-of-line supervisory
resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4
or 5, depending upon the type of smoke detector being used.
Observe proper polarity, 3 (+), 4 (–) when attaching to the release
device’s terminal board.
NOTE:
Make certain that the factory-
installed jumper between terminal positions 5 and 6 remains in
place.
This option is a supervised, current-limited circuit.
OR
Normally Closed “4-Wire,” Class B Style A Initiating Devices
After removing the factory-installed jumper between terminal
positions 5 and 6, connect wiring from N/C 4-Wire initiating
device loop to positions 5 and 6 (Figure 6). This option is a
supervised, current-limited circuit.
NOTE:
Make certain that the
factory-installed resistor between positions 3 and 4 remains in
place.
NOTE:
End-of-line devices must be installed adjacent and after
the last initiating device. Initiating device loops are supervised
and cannot be direct series or paralleled between multiple release
devices or shared with other alarm equipment. For proper wiring
configurations from multiple smoke detectors or signaling for
simultaneous closure on multiple doors, call technical support,
1-888-528-7870. Incorrect wiring between devices may cause
damage to the release control circuit and void warranty.
OR
Relay Module Installation
as described on the following page.
WIRING
To prevent possible SERIOUS INJURY or DEATH:
• End-of-line devices MUST be installed for supervision of
electrical power to 4-wire smoke detector.
• DO NOT install this device on a motorized door without an
electric safety edge.
WARNING
FIGURE 4
10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)
– IN/OUT
+ OUT
+ IN
– IN/OUT
+ OUT
+ IN
24Vdc Power
from Terminal
Strip
3
4
NOTE:
Follow this method of
attachment when using
LM2W-B,
LM2WT-B, or other 2-wire 24Vdc
smoke detectors.
Power from
Control Panel
(–)
(+)
Terminal Strip
3
4
COM
NO
– IN/OUT
+ OUT
+ IN
COM
NO
– IN/OUT
+ OUT
+ IN
LMEOLR1224
12/24 Vdc
EOL Relay
10k Ohm @ 1/2 watt
Supervisory Resistor
(LMEOLRES-10)
NOTE:
Follow this method of attachment when using
LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors.
Purple
Power from
Control Panel
(–)
(–)
(–)
N/C
C
C
N/C
(+)
(+)
(+)
LMEOLR1224
12/24 Vdc
EOL Relay
Terminal Strip
5
6
NOTE:
Generic version of a N/C
4-wire smoke detector is shown.
IMPORTANT:
When using 4-wire smoke detectors with this
device, the smoke detectors must be powered from a source
other than the release device, such as an approved UL 1481
regulated power supply providing battery backup support.
Power from
Control Panel
(+)
(–)
(–)
(+)
(–)
(+)
(–)
Alarm
Contacts
Style A
(
N/O
)
(+)
LMEOLR1224
12/24 Vdc
EOL Relay
10k Ohm @ 1/2 watt
Supervisory Resistor
(LMEOLRES-10)
NOTE:
Follow this method of attachment when using
LM1424, LM1412, or other N/O 4-wire smoke detectors.
Terminal Strip
3
4
IMPORTANT:
When using 4-wire smoke detectors with this device,
the smoke detectors must be powered from a source other than the
release device, such as an approved UL 1481 regulated power supply
providing battery backup support.
FIGURE 5
FIGURE 3
FIGURE 6